       IMPORTANT -  CE  &  SAFETY REQUIREMENTS 

Product must be DIN rail mounted, inside a suitable enclosure providing environmental protection to IP65 or greater.
To maintain CE EMC requirements , input  wires  must be less than 30 meters.
The product contains no serviceable parts , or internal adjustments. no attempt must be made to repair this product. Faulty units must be returned to 

supplier for repair.
This product must be installed by a qualified person. All electrical wiring must be carried out in accordance with the appropriate regulations for the 

place of installation.
Before attempting any electrical connection work, please ensure all supplies are switched off.

ABSOLUTE MAXIMUM OPERATING CONDITIONS (To exceed may cause damage to the unit) :-

Supply Voltage

± 30 VDC  (Protected for over voltage and reverse connection)

Current with over voltage

± 200 mA

Input Voltage

± 5 V  between any terminals

Input Current

± 100 mA between terminals 7 & 10

Ambient

Temperature (-30 to 75) °C  Humidity (10 to 95) % RH (Non condensing)

CONFIGURATION

M-CONFIG SOFTWARE

Disk or download @ 

www.statInst.com

COMPUTER

IMPORTANT - The SEM1603TC can be configured while connected and powered, but  a portable battery powered computer must be used to avoid the effects of 

ground loops.

The transmitter may be purchased pre-configured, if specified at the time of order. The user can re-configure the transmitter by using our USB 
configurator tool (USB KIT). Connect the configurator to the PC USB port then connect the solid gray wire to terminal 5 (+) and the black striped wire 
to terminal 4 (-). Then run the Status Instruments USB_CONFIG software, available free from www.statinst.com. The USB port supplies power to the 
SEM1603TC during configuration, no additional wiring is required. The following parameter can be configured by simply entering as prompted by the 
software package. 

· Input type (K, J, E, N, T, R, S, mV)
· Low range 
· High range
· Units      (°C, °F, mV)
· Burnout (direction of output current on sensor burnout)

Factory default:

     Input type

= K

     High Range

= 1000

     Low Range

= 0

     Burnout

= UPSCALE

     Units

= °C

PRODUCT SPECIFICATION

Please refer to the product data sheet for full specification, available to down load at www.statinst.com.

RECEIVE AND UNPACKING

Please inspect the packaging and instrument thoroughly for any signs of transit damage. If the instrument has been damaged, please notify your supplier immediately.

                Status Instruments Inc,  PO Box 548,  456 Park Avenue,  Scotch Plains, NJ  07076

Web Page:  www.statinst.com    Tel: (800) 700-3272    Fax:  (800) 700-5468   email: [email protected]

SEM1603TC USER GUIDE

DIN RAIL MOUNTED TRANSMITTER
THERMOCOUPLE INPUT
TWO WIRE (4 to 20) mA OUTPUT

Every effort has been taken to ensure the accuracy of this document, however we do not accept responsibility for damage, injury, loss or expense resulting from errors and omissions, and we reserve the right of amendment without notice.

Important - Please read this document before installing.

Vs

Loop 
Load

+

-

+

-

10

9

8

7

SEM1603TC

5

4

2 Wire (4 to 20) mA Output

SEM1603TC

USB CONFIGURATOR

4

5

m

V

+

+

-

-

8

7

7

8

T/C

Input

SEM1603TC_User_GuideUSA_5-08

Reviews: