background image

D2133_01_04 CN5082 SEM110  User Guide

 

The Pt100 sensor shown as an example would normally take the form of a 
probe assembly with a three wire output. Refer to connection drawing for 
other connection types. The output loop shows a 24 V DC power supply 
used to provide loop excitation, the transmitter and a load all connected in 
series. The load symbol represents other equipment in the loop e.g. 
indicators, controllers, loggers etc. Sometimes these instruments come 
with the 24 V supply built in as standard, this simplifies wiring and reduces 
cost.  Care must be taken when designing the (4 to 20) mA circuit to 
ensure that the total burden of the loop, that is the total voltage  
requirements of all the equipment in the loop added together, does not 
exceed the power supply voltage. If a number of instruments are 
connected in the loop, ensure that only one instrument is tied to ground. 
Grounding the loop at two points will result in shorting out part of the loop 
and therefore any instruments in that part of the loop will not operate. 
 

4.0 Calibration 

 
Calibration is only recommended when the user has access to suitable 
equipment, together with a reasonable knowledge of instrumentation 
calibration techniques. The following instructions act as a guideline to 
calibration. 
 
4.1 

A precision calibrator will be required, to simulate the type of 
sensor the transmitter is designed for, together with a set of 
tables giving the sensor output against process variable, (e.g. 
resistance against temperature for a PT100 sensor). A 
precision digital current meter together with a 24 V DC supply 
will also be needed. Read the SEM110 label to establish the 
transmitter range i.e. the process variable input for 4 mA and 
20 mA.  The side label also indicates the location of the span 
and zero pots. 

 
4.2 

Connect calibrator to input terminals, using the correct 
compensation wire for thermocouples inputs and three wire 
connection for RTD inputs.  Connect the output positive to +24 
V, negative to 0 V via current meter. Turn power on. 

 
4.3 

Set simulator to 4 mA process variable and adjust ZERO 
trimmer for 4.000 mA output. ±0.002mA 

 
4.4 

Set simulator to 20 mA process variable and adjust SPAN 
trimmer for  20.000 mA output ±0.002 mA. 

 
4.5 

Repeat steps 4.3 and 4.4 until both points are in calibration. 

 
4.6 

Turn power off and remove calibration equipment. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

5.0 SEM110X\*  VERSIONS -  FOR USE IN POTENTIALLY EXPLOSIVE 
ATMOSPHERES 

 

5.1 ATEX Certificate 

 
The SEM110X/* models has been issued with a EC-type examination 
certificate, confirming compliance with the European ATEX directive 
94/9/EC for :- 
 
Intrinsic safety 

 

II 1 G EEx ia  IIC T5.  

 
The equipment bears the Community Mark and subject to local codes of 
practice, may be installed in any of the European Economic Area (EEA) 
member countries. The SEM110X housing is coloured light blue to identify 
the equipment as suitable for Hazardous area use. The equipment must 
be installed and maintained in accordance with local requirements for 
electrical equipment for use in potentially explosive atmospheres, eg 
EN60079-14 & EN60079-17. This instruction sheet describes installation 
which conforms with BS EN60079-14 & BS EN60079-17 Electrical 
Installation in Hazardous Areas. When designing systems outside the UK, 
the local Code of Practice should be consulted.  
 

5.2 Atex marking 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Common Information 
 
Manufacturer  

 

Status Instruments Ltd  

Type Number  

 

SEM110X/P 

 

 

 

SEM110X/TC 

 

 

 

SEM110X/W 

 
CE Marking 

 

0891 

 
Explosive Protection Marking 
 
(Type ia) Intrinsic Safety 
 
II   1  

 

 

Equipment Group and category 

 

 

Type of explosive atmosphere (Gas) 

EEx ia IIC T5 

 

Intrinsic safety information 

TRL03ATEX21004X   

Certificate reference 

 

5.3 Special Conditions for Safe Use 

 
As indicated by the Certificate Reference "X" suffix, special conditions 
apply for safe use for both intrinsic safety and energy limitation 
applications.   They are as follows:- 
 

 
 

5.4 Zones, Gas Groups, and T rating. 

 
When connected to a approved system the SEM110X/* may be installed 
in:- 
 
Zone 0 

explosive gas air mixture continuously present 

Zone 1 

explosive gas air mixture likely to occur in normal use 

Zone 2 

explosive gas air mixture not likely to occur and if it does, it will 
only occur for a short time. 

 
Be used in gas groups;- 
 
Group A 

propane 

Group B 

ethylene 

Group C 

hydrogen 

 
Allowable Temperature classification / ambient temperature:-  
 
Intrinsic safety  (Type ia) 
 
Class 

 

 

 

 

T5 100°C : Ta = -20°C to +40°C 
T4 135°C : Ta = -25°C to +55°C 
T3 200°C : Ta = -25°C to +55°C 
T2 300°C : Ta = -25°C to +55°C 

 

 

T1 450°C : Ta = -25°C to +55°C 

 

 

5.5 Environmental Protection 

 
This equipment must be housed in an enclosure which provides a degree 
of protection of at least IP54. The enclosure must be suitable for the 
atmosphere and environment in which it is installed (eg If of plastic 
material, must be resistant to chemical corrosion, UV light, temperature, 
humidity etc.)  
 

5.6 Maintenance  

 
This intrinsically safe equipment contains no user serviceable, adjustable 
or replaceable parts. No attempt should be made to repair a faulty 
SEM110X/* transmitter, all units must be returned to the manufacture for 
repair or replacement.  Attempt service or

 

replacement of parts may 

invalidate the explosive protection features of the equipment. 
 

5.7 Connection Diagram 

 
 
 
 
 
 
 
 
 
 
 
 
They equipment must be electrically connected as shown below:- 
 
SEM110X\*  Working Parameters  
 
Ui 

28 V 

I i 

93.3 mA 

Pi 

0.653 W 

Ci 

0 nF 

Li 

0 uH 

-

SEM 110X

C ALIBR ATO R

D C

+

-

+ 24V

A

SENSOR

SEM110X

1

4

5

                        2

BARRIER
Maximum
output

Vo    30V
Io    100mA
Po   750mW

DC
SUPPLY
+

-

Reviews: