background image

11

Inner Wall 

Plate

Screws 

& Sealant

Outer 

Wall

Plate

HOT

Screws

Vent Cap

Screws

Sealant

Slope down 1/4” 

per foot

Figure 7

Vertical Installation

9.  Position and fasten the inner wall plate to the inside 

wall using an appropriate fastener for the specific wall  

construction.  Apply silicone sealant between the inner  

wall plate and the inside wall.  

10. Make certain the 5” telescoping pipe has been fully  

engaged onto the 5 inch elbow.  Drill two 1/8” holes 

180° apart at the junction of the two joints. Secure 

with four #8 sheet metal screws and apply silicone 

sealant to the seams.  Make sure all the 5” pipe joints 

are sealed including the joint to the collar on the water 

heater’s air supply box (See Figure 8).

Optional Vertical Extension Kit

Installations requiring dimension “A” to be greater than 

62.75” (40 Gallon) or 71.00” (50 Gallon) will require the 

use of the optional vertical extension kit. The maximum 

height of the “A” dimension cannot exceed 98 inches. If the 

“A” dimension for your application is less than 98 inches, 

you will have to cut the 3 and 5 inch pipes in the vertical 

extension kit to the correct length. For example, if your 

applicable “A” distance is 80 inches, then 98 inches - 80 

inches = 18 inches. Therefore, you will need to cut 18 

inches from both the 3 and 5 inch vertical extension pipes. 

DO NOT CUT THE CRIMPED END OF THE 5 INCH PIPE.
After cutting both the pipes to the proper size, place the 3” 

vertical extension pipe over the flue pipe reducer on the 

upper air box and press it firmly downward until seated. 

Using a level, make sure the extension tube is pointing 

straight up. Drill 4 holes 90° apart with a 1/8” drill bit and 

fasten with four #8 sheet metal screws (provided). Apply 

silicone sealant to the seam.
Place the uncrimped end of the 5 inch extension pipe 

over the 3 inch extension pipe and seat it onto the collar 

on the air box. Making sure the 3 inch extension pipe is 

centered in the 5 inch pipe, drill four holes 90° apart with 

the 1/8” drill bit and fasten with four #8 sheet metal screws 

(provided). Apply silicone sealant to the seam. Place the 

flared end of the 3 inch elbow over the 3 inch extension 

pipe and press it firmly downward until seated. Drill four 

holes 90° apart with the 1/8” drill and fasten with four #8 

sheet metal screws (provided). Apply silicone sealant to 

the seam.
Install the 5 inch elbow over the 3 inch elbow and seat 

it down onto the crimped end of the 5 inch extension 

pipe. Temporarily place the 5 inch telescoping pipe onto 

the 5 inch elbow and adjust it to give a 1/4 inch per foot 

downward slope to the outside wall. Secure the 5 inch 

elbow to the extension pipe by drilling four holes 90° 

apart with the 1/8” drill and inserting four #8 sheet metal 

screws. Apply silicone sealant to the joint. Place the inner 

wall cover plate over the 5 inch elbow. This plate will be 

positioned later. Proceed to step 4.

Through The Roof Venting*

1.  Center the heater directly under the roof opening. This 

vent system must be installed vertically only.

2.  All the pipes needed to assemble the vent are 

included in the kit. Do not add to the length of the 

vent system. The total height is limited to 15 feet 

on a 50-gallon heater (See Figure 8). The 40-gallon 

heater is 8 and1/4” shorter. The total 15-foot height 

must stick through the roof a minimum of 2 feet. If 

the height needed is less than 15 feet, determine the 

height needed and subtract that from 15 feet. That 

amount needs to be cut off one of the 3” pipes and 5” 

pipes. Cut the non-flared end of the 3” pipe and the 

uncrimped end of the 5” pipe.

3.  Assemble the kit from the top down starting with the  

termination.  Attach a 3” pipe using 4 #8 sheet metal  

screws 90° apart and seal the joint with sealant. Then 

attach the 5” section in the same manor. Drill 1/8”    

pilot holes for the screws. Continue until the full length 

is assembled. Put the telescoping 5” section on last.

4.  Place the heater in position, feed the vent assembly  

down through the roof with the flashing in place, and  

allow it to rest with the 3” pipe attached to the 3” vent 

terminal on the heater. Use screws and sealant to    

secure that joint. Extend the 5” telescoping section to 

connect to the 5” termination on the heater. Secure   

that joint with screws. Seal that joint and the sliding   

joint with silicone to make an airtight assembly. 

5.  Secure the flashing and vent assembly to the roof.
(*Through the Roof Venting Kit available from manufacturer)

Roof Jack Assembly

8 Ft. Min.
15 Ft. Max

Roof Flashing

Secure All 
Connection
s with 
Screws and 
Apply 
Silicone 
Sealant

2 Ft. Min.

From Any Object 

within A 10 Foot 

Horizontal Radius

Figure 8
Through the Roof Venting

VAC

Summary of Contents for Ultra Low Nox Series

Page 1: ...losion may result causing property damage personal injury or death INSTALLER AFFIX THESE INSTRUCTIONS TO OR ADJACENT TO THE WATER HEATER OWNER RETAIN THESE INSTRUCTIONS AND WARRANTY FOR FUTURE REFEREN...

Page 2: ...use this appliance if any part has been under water Immediately call a qualified person Water heaters sub jected to flood conditions or any time the gas controls main burner or pilot have been submerg...

Page 3: ...tally vented gas fueled heat ing appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The s...

Page 4: ...uctions thoroughly before attempting the installation or operation of this water heater Do not discard this manual You or future users of this water heater will need it for future reference IMPORTANT...

Page 5: ...quids in the vicinity of this or any other appliance Storage of or use of gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance can result in serious injury or d...

Page 6: ...ons The water heater should be located in an area not subject to freezing temperatures Water heaters located in unconditioned spaces i e attics basements etc may require insulation of the water piping...

Page 7: ...ubbles will show a leak Correct any leak found Gas Pressure IMPORTANT The gas supply pressure must not exceed the maximum supply pressure as stated on the water heater s data plate The minimum supply...

Page 8: ...ating the water heater next to an outside wall All necessary components are supplied for the standard through the wall installation Optional vertical and horizontal extension kits are available for in...

Page 9: ...ight for all water heaters is 90 Minimum height for 40 Gallon water heaters 68 and minimum height for 50 Gallon water heaters is 76 Figure 4A Dim B is measured from the center of water heater to the o...

Page 10: ...e the 3 tube located in the vent cap into the end of the 3 telescoping tube See Figure 7 Drill two holes 180 apart with a 1 8 drill bit and secure with two 8 sheet metal screws Apply sealant to the jo...

Page 11: ...with the 1 8 drill and fasten with four 8 sheet metal screws provided Apply silicone sealant to the seam Install the 5 inch elbow over the 3 inch elbow and seat it down onto the crimped end of the 5 i...

Page 12: ...ffit F Clearance to outside corner U S Installation Clearance in accordance with local installation codes and the requirements of the gas supplier G 12 in 30 cm min clearance to inside corner formed b...

Page 13: ...ure of the water by mixing cold and hot water and are readily available for use 4 If installing the water heater in a closed water system install an expansion tank in the cold water line as specified...

Page 14: ...rson include licensed plumbers authorized gas company personnel and authorized service personnel Do not plug valve Do not remove valve Failure to follow these instructions can result in death or explo...

Page 15: ...installed to allow complete drainage of both the valve and discharge line T P Relief Valve and Pipe Insulation Some Models 1 Locate the temperature and pressure relief valve on the water heater also...

Page 16: ...tem Otherwise these bubbles will be trapped in the air handler heat exchanger coil reducing the efficiency Do not connect the water heater to any system or components previously used with non potable...

Page 17: ...rough the Roof Venting Through the roof venting has a 15 foot maximum height for the 50 Gallon direct vent water heater and a maximum of 14 3 1 4 for the 40 Gallon direct vent water heater Vent pipe s...

Page 18: ...Pilot lights 4 Once the Pilot is lit continue to hold the Control Knob in until the Status Light begins to blink 5 Release Control Knob and set Knob to desired temperature setting Hot is approximatel...

Page 19: ...age personal injury or loss of life TO TURN OFF GAS TO APPLIANCE 1 Turn the gas control temperature knob counterclockwise to the OFF setting The status light will stop blinking and stay on for a short...

Page 20: ...t This water heater s temperature control has been designed to accurately regulate the water temperature However under certain operating conditions the water temperature may temporarily exceed the dia...

Page 21: ...ain threshold 35 minutes 1 minute 5 seconds 2 seconds 1 second instantaneous 45 minutes 5 minutes 25 seconds 5 seconds 2 seconds 1 second U S Government Memorandum C P S C Peter L Armstrong Sept 15 19...

Page 22: ...approximately 55 F This setting is recommended when the water heater is not in use for a long period of time This effectively turns the controller temperature setting down to a temperature that preven...

Page 23: ...Temperature Control System If the ECO has functioned the gas control valve thermostat should be replaced by a qualified person Contact your local dealer for service information Anode Rod Water Odor Ea...

Page 24: ...d pilot burner Check for a soft blue flame Leaking or damaged water and gas piping Presence of flammable or corrosive materials in the installation area Presence of combustible materials near the wate...

Page 25: ...e thermopile wires from the gas control valve thermostat See Figures 22 23 6 Grasp the manifold tube and push down slightly carefully remove the burner door assembly from the burner compartment NOTE B...

Page 26: ...pilot nut IMPORTANT Keep the pilot orifice in the pilot when making the connection DO NOT operate the water heater without the pilot orifice installed 8 Push the new pilot assembly connectors through...

Page 27: ...y WARNING Replace manifold component block if missing or removed Replace door gasket if damaged Failure to follow these instructions can Replace viewport if glass is missing or damaged Tighten all bur...

Page 28: ...water heater Follow the Lighting Instructions on page 18 If additional information is required contact Residential Technical Assistance Operational Checklist TROUBLESHOOTING CHART 4 No leaks at pilot...

Page 29: ...erature dial to desired setting 6 Install adequate heater 7 Correct piping dip tube must be in cold inlet 8 Advise customer DRIP FROM RELIEF VALVE 1 Excessive water pressure 2 Heater stacking 3 Closed...

Page 30: ...re contact a qualified person 8 FLASHES This condition only appears if the gas control temperature knob has been turned off and the thermopile continued to produce electric power This condition can oc...

Page 31: ...E 16 DRAIN VALVE 17 ANODE ROD 18 VIEWPORT 19 DOOR SCREW 20 BURNER DOOR ASSEMBLY NAT GAS 21 MANIFOLD COMPONENT BLOCK 22 OUTER DOOR 23 OPTIONAL VENT GUARD SEE PAGE 12 KIT 6907245 Pictured on next page W...

Page 32: ...e burner gasket door pilot tube manifold component block with retainer clip temperature sensor and pilot assembly Natural Gas Low Nox Item 20a Pilot assembly kit which contains the pilot electrode and...

Page 33: ...33 NOTES...

Page 34: ...34 NOTES...

Page 35: ...35 NOTES...

Page 36: ...36 Copyright 2013 All Rights Reserved Printed in the U S A...

Reviews: