15
VENTING
WARNING
THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST
BE FOLLOWED TO AVOID CHOKED COMBUSTION OR
RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE
SOOTING OR RISKS OF FIRE AND ASPHYXIATION.
WARNING
NEVER OPERATE THE HEATER UNLESS IT IS VENTED TO
THE OUTDOORS AND HAS ADEQUATE AIR SUPPLY TO AVOID
RISKS OF IMPROPER OPERATION, FIRE, EXPLOSION OR
ASPHYXIATION.
CAUTION
DO NOT TERMINATE THE VENTING WHERE NOISE FROM THE
EXHAUST OR INTAKE WILL BE OBJECTIONABLE. THIS
INCLUDES LOCATIONS CLOSE TO OR ACROSS FROM WINDOWS
AND DOORS.
FIGURE 33
VENT TERMINALS
The vent system must terminate so that proper clearances are
maintained as cited in local codes or the current edition of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54.
The SRT80-120NE series is designed with an internal vent
construction. The exhaust vent terminal and the inlet air terminal
are located on the sides of the appliance. Do not add vent pipe to
the appliance, see Figure 33.
Assure the exhaust vent terminal is not in a public area where the
hoods are exposed. The exhaust vent terminal gets very
HOT
during operation and can cause burns. Please use caution when
working around the exhaust vent terminal.
It is imperative that the area around the vent terminal hoods are
kept clear from obstructions so plenty of fresh air is available for
combustion.
The vent shall terminate a minimum of 12" (30.5 cm) above expected
snowfall level to prevent blockage of vent termination.
WARNING
USE ONLY THE VENT TERMINALS SUPPLIED WITH THIS UNIT.
TERMINATION OF A VENT SYSTEM WITH A DEVICE OTHER
THAN THE SUPPLIED VENT TERMINATIONS WILL AFFECT
SYSTEM PERFORMANCE AND RESULT IN A SAFETY HAZARD.
PRESSURE SWITCHES
The SRT80-120NE is provided with three pressure switches.
These switches are essential to the safe and proper operation of
the unit. All switches are wired in series. The controller is set up to
shut the unit down whenever there is a failure of any of the switches.
CAUTION
THE WATER HEATER IS POLARITY SENSITIVE. BEFORE
APPLYING ELECTRICITY TO THIS HEATER BE CERTAIN THAT
SUPPLY NEUTRAL WIRE TO GROUND CHECK INDICATES ZERO
VOLTAGE.
GAS PIPING
Contact your local gas service company to ensure that adequate
gas service is available and to review applicable installation codes
for your area.
TABLE 3
MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR
(Based upon a Pressure Drop of 0.5 inch Water Column
and 0.6 Specific Gravity Gas
Size the main gas line in accordance with Table 3. The figures
shown are for straight lengths of pipe at 0.5 in. (125 kPa) W.C.
pressure drop, which is considered normal for low pressure
systems. Note that fittings such as elbows and tees will add to the
pipe pressure drop.
CAUTION
DO NOT USE FLEXIBLE GAS PIPING.
LENGTH
NORMAL IRON PIPE SIZES (INCHES)
IN
INPUT IN THOUSANDS BTU/HR
FEET
1/2"
3/4"
1"
1 1/4" 1 1/2"
2"
2 1/2"
3"
4"
10
175
360
680
1400
2100
3960
6300
11000 23000
20
120
250
485
950
1460
2750
4360
7700
15800
30
—
200
375
770
1180
2200
3520
6250
12800
40
—
170
320
660
990
1900
3000
5300
10900
50
—
151
285
580
900
1680
2650
4750
9700
60
—
138
260
530
810
1520
2400
4300
8800
70
—
125
240
490
750
1400
2250
3900
8100
80
—
—
220
460
690
1300
2050
3700
7500
90
—
—
205
430
650
1220
1950
3450
7200
100
—
—
195
400
620
1150
1850
3250
6700
125
—
—
175
360
550
1020
1650
2950
6000
150
—
—
160
325
500
950
1500
2650
5500
175
—
—
145
300
460
850
1370
2450
5000
200
—
—
135
280
430
800
1280
2280
4600
LENGTH
NORMAL IRON PIPE SIZES (INCHES)
IN
INPUT IN KW
METERS
1/2"
3/4"
1"
1 1/4" 1 1/2"
2"
2 1/2"
3"
4"
3.0
51
105
199
410
615
1160
1845
3221
6735
6.1
35
73
142
278
428
805
1277
2255
4626
9.1
—
59
110
225
346
644
1031
1830
3748
12.2
—
50
94
193
290
556
878
1552
3192
15.2
—
44
83
170
264
492
776
1391
2840
18.3
—
40
76
155
237
445
703
1259
2577
21.3
—
37
70
143
220
410
659
1142
2372
24.4
—
—
64
135
202
381
600
1083
2196
27.4
—
—
60
126
190
357
571
1010
2108
30.5
—
—
57
117
182
337
542
952
1962
38.1
—
—
51
105
161
299
483
864
1757
45.7
—
—
47
95
146
278
439
776
1610
53.3
—
—
42
88
135
249
401
717
1464
61.0
—
—
40
82
126
234
375
688
1347
Summary of Contents for ROOFTOP SRT80 120NE
Page 18: ...18 FIGURE 36 ...