background image

14

THERMAL EXPANSION

Water supply systems may, because of such events as high line
pressure, frequent cut-offs, the effects of water hammer among others,
have installed devices such as pressure reducing valves, check valves,
back flow preventers, etc. to control these types of problems. When
these devices are not equipped with an internal by-pass, and no
other measures are taken, the devices cause the water system to be
closed. As water is heated, it expands (thermal expansion) and closed
systems do not allow for the expansion of heated water.

The water within the water heater tank expands as it is heated and
increases the pressure of the water system. If the relieving point of
the water heater’s temperature-pressure relief valve is reached, the
valve will relieve the excess pressure. 

The temperature-pressure

relief valve is not intended for the constant relief of thermal
expansion.

 This is an unacceptable condition and must be corrected.

It is recommended that any devices installed which could create a
closed system have a by-pass and/or the system have an expansion
tank or device to relieve the pressure built by thermal expansion in
the water system. Expansion tanks are available for ordering through
a local plumbing contractor. Contact the local water heater supplier
or service agency for assistance in controlling these situations.

STRANGE SOUNDS

Possible noises due to expansion and contraction of some metal
parts during periods of heat-up and cool-down do not necessarily
represent harmful or dangerous conditions.

OPERATIONAL CONDITIONS

WATER ODOR

In each water heater there is installed at least one anode rod (see
parts sections) for corrosion protection of the tank. Certain water
conditions will cause a reaction between this rod and the water.
The most common complaint associated with the anode rod is one
of a “rotten egg smell” in the hot water. This odor is derived from
hydrogen sulfide gas dissolved in the water. The smell is the result
of four factors which must all be present for the odor to develop:

A. A concentration of sulfate in the supply water.
B. Little or no dissolved oxygen in the water.

C. A sulfate reducing bacteria which has accumulated within the

water heater (this harmless bacteria is nontoxic to humans).

D. An excess of active hydrogen in the tank. This is caused by the

corrosion protective action of the anode.

Smelly water may be eliminated or reduced in some water heater
models by replacing the anode(s) with one of less active material, and
then chlorinating the water heater tank and all hot water lines.  Contact
the local water heater supplier or service agency for further information
concerning an Anode Replacement Kit and this chlorination treatment.
If the smelly water persists after the anode replacement and
chlorination treatment, we can only suggest that chlorination or aeration
of the water supply be considered to eliminate the water problem.

Do not remove the anode leaving the tank unprotected. By doing
so, all warranty on the water heater tank is voided.

“AIR” IN HOT WATER FAUCETS

HYDROGEN GAS: Hydrogen gas can be produced in a hot water
system that has not been used for a long period of time (generally
two weeks or more).  Hydrogen gas is extremely flammable and
explosive.  To prevent the possibility of injury under these conditions,
we recommend the hot water faucet, located farthest away, be
opened for several minutes before any electrical appliances which
are connected to the hot water system are used (such as a
dishwasher or washing machine).  If hydrogen gas is present, there
will probably be an unusual sound similar to air escaping through
the pipe as the hot water faucet is opened.  There must be no smoking
or open flame near the faucet at the time it is open.

HIGH WATER TEMPERATURE SHUT OFF SYSTEM

A non-adjustable high temperature limit control operates

before steam temperatures are reached. The high limit is
in the same area as the upper thermostat and must be

reset manually when it operates. BECAUSE THE HIGH LIMIT
OPERATES ONLY WHEN ABNORMALLY HIGH WATER
TEMPERATURES ARE PRESENT, IT IS IMPORTANT THAT A

QUALIFIED SERVICE AGENT BE CONTACTED TO DETERMINE
THE REASON FOR OPERATION BEFORE RESETTING.

• Turn off the heater electrical supply. Do not attempt to reset

thermostat with power on.

• Remove the screw(s) securing the outer door and remove door.

• Remove or fold up the insulation  to expose the reset button.

• Reset the high limit by pushing in the red button marked “RESET”.

• Replace the insulation so that it completely covers the thermostat

and element.

• Replace the outer door.

• Turn “ON” electric power to the water heater.

FOR YOUR INFORMATION

Summary of Contents for 120 Series

Page 1: ...HOULDBEDIRECTEDTOTHELOCALDEALERFROMWHOMTHEWATERHEATERWAS PURCHASED IFYOUARE UNSUCCESSFUL PLEASE WRITETO THE COMPANYLISTED ON THE RATING PLATE ON THE WATER HEATER GAMA certification applies to all residential electric water heaters with capacities of 20 to 120 gallons Input rating of 12 Kw or less LISTED Instruction Manual RESIDENTIAL ELECTRIC WATER HEATERS MODELS 6 120 FOR POTABLE WATER HEATING ON...

Page 2: ...Qualified Installer A qualified installer must have ability equivalent to a licensed tradesman in the fields of plumbing and electrical installation of these appliances This would include a thorough understanding of the requirements of the National Electrical Code and applicable local electrical and plumbing codes and tools necessary to confirm proper installation and operation of the water heater...

Page 3: ...3 GENERAL SAFETY ...

Page 4: ... Carefully plan your intended placement of the water heater INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED PLUMBING AND ELECTRICAL WORK ARE REQUIRED Examine the location to ensure the water heater complies with the Facts to Consider About the Location section in this manual 5 For California installation this water heat...

Page 5: ...ATER LOCATION SEE INSTALLING THE NEW WATER HEATER SECTION INSTALL THERMAL EXPANSION TANK OR DEVICE IF WATER HEATER IS INSTALLED IN A CLOSED WATER SYSTEM ELECTRICAL CONNECTIONS MAYBE LOCATED ON THE TOP OR SIDE REFER TO YOUR UNIT ACTUAL MODEL AND ILLUSTRATION MAY VARY DEPENDENT ON MODEL CAPACITY AND TYPE SOME MODELS HAVE ALTERNATE INLET OUTLET AND T P VALVE LOCATIONS THESE ALTERNATE LOCATIONS ARE ID...

Page 6: ...e available from your local plumbing contractor Consult a Qualified Installer or Service Agency Follow mixing valve manufacturer s instructions for installation of the valves Before changing the factory setting on the thermostat read the Temperature Regulation section in this manual FACTS TO CONSIDER ABOUT THE LOCATION Carefully choose an indoor location for the new water heater because the placem...

Page 7: ...em Expansion tanks are available for ordering through a local plumbing contractor Contact the local water supplier and or a service agency for assistance in controlling these situations 3 The water heater should be located so it is not subject to physical damage by moving vehicles or area flooding Installation of the water heater must be accomplished in such a manner that if the tank or any connec...

Page 8: ...nection Do not solder the cold water supply line directly to the cold water inlet it will harm the dip tube and damage the tank FIGURE 3 WATER PIPING PRESSURE TEST This section is only for the manufacturer installing the water heater when the installation is to comply with H U D Standards When testing the water ways H U D Standards state Water distribution system All water piping in the water dist...

Page 9: ... electrical part The discharge opening must not be blocked or reduced in size under any circumstances Excessive length over 30 feet 9 14 m or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve No valve or other obstruction is to be placed between the relief valve and the tank Do not connect tubing directly to discharge drain unless a 6 inch air gap is...

Page 10: ...n the cold water supply valve to the water heater NOTE The cold water supply valve must be left open when the water heater is in use 3 To insure complete filling of the tank allow air to exit by opening the nearest hot water faucet Allow water to run until a constant flow is obtained This will let air out of the water heater and the piping 4 Check all water piping and connections for leaks Repair ...

Page 11: ...11 WIRING DIAGRAMS FOR ACTUAL WIRING CIRCUIT OF UNIT REFERENCE CIRCUIT TYPE LISTED ON RATING PLATE FIGURE 6 ...

Page 12: ...ut off the electric power when working on the water heater This could be with a circuit breaker or fuse block in the entrance box or a separate disconnect switch 2 Install and connect a circuit directly from the main fuse or circuit breaker box This circuit must be the right size and have its own fuse or circuit breaker 3 If metal conduit is used for the grounding conductor A The grounding electro...

Page 13: ...ured by hot water than others These include the elderly children the infirm or physically mentally disabled If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap then you must take special precautions In addition to using the lowest possible temperature setting that satisfies your hot...

Page 14: ... harmless bacteria is nontoxic to humans D An excess of active hydrogen in the tank This is caused by the corrosion protective action of the anode Smelly water may be eliminated or reduced in some water heater models by replacing the anode s with one of less active material and then chlorinating the water heater tank and all hot water lines Contact the local water heater supplier or service agency...

Page 15: ...The submerged rod sacrifices itself to protect the tank Instead of corroding the tank water ions attack and eat away the anode rod This does not affect the water s taste or color Therodmustbemaintainedtokeepthetankinoperatingcondition NOTE Artificially softened water is exceedingly corrosive because the process substitutes sodium ions for magnesium and calcium ions The use of a water softener may ...

Page 16: ...s to the new thermostat NOTE Some of the terminals may require straight in wiring through an eye opening If wires are now looped recut and strip wire 3 8 to a straight length and insert 8 Put plastic terminal cover back in place 9 Replace the insulation to cover the thermostat 10 Replace outer door then turn the electric power on ELEMENT CLEANING REPLACEMENT NOTE These instructions are written for...

Page 17: ...erminal cover from the thermostat The terminal cover can now be removed from the thermostat FIGURE 17 7 Disconnect the two wires on the element and unscrew the old element from the tank FIGURE 18 8 Clean the area around the element opening Remove any sediment from or around the element opening and inside the tank 9 If you are cleaning the element you have removed do so by scraping or soaking in vi...

Page 18: ...wires to the element and then check to make sure the thermostat remains firmly against the surface of the tank FIGURE 20 16 Replace terminal cover on thermostat making sure the locking tabs on the terminal cover are in place 17 Replace the insulation so that it covers the thermostat and element see Figure 21 18 Replace outer door 19 Turn ON electric power to water heater FIGURE 21 DRAIN VALVE WASH...

Page 19: ...ide of the tank may be condensation due to the panel or insulation not being in place F Water from a drain valve may be due to the valve being slightly opened G The drain valve may be leaking at the tank fitting H Water in the water heater bottom or on the floor may be from condensation loose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible wa...

Page 20: ...ause s Corrective Action These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES Improperly sealed hot or cold supply connection relief valve or drain valve Leakage from other appliances or water lines No power to heater High Temperature Limit Switch open Non functioning upper thermostat Non functioning thermostats Non functioning lower element Improper calibrat...

Page 21: ... P Insulation Instruction Manual If Applicable Not Illustrated Now that you have purchased this water heater should a need ever exist for repair parts or service simply contact the company it was purchased from or the manufacturer listed on the rating plate on the water heater Be sure to provide all pertinent facts when you call or visit Selling prices will be furnished on request or parts will be...

Page 22: ...be found on the rating plate located above or adjacent to outer door Key No Part Description 1 Temperature Pressure Relief Valve 2 Outlet Nipple Assembly 3 Inlet Nipple 4 Junction Box Cover 5 Upper and Lower Element 6 Element Gasket 7 Thermostat Bracket ea 8 Lower Thermostat 9 Terminal Cover 10 Lower Thermostat w Hi Limit 11 Terminal Cover 12 Lower Outer Door 13 Upper Outer Door 14 Upper Thermosta...

Page 23: ...is water heater should a need ever exist for repair parts or service simply contact the company it was purchased from or the manufacturer listed on the rating plate on the water heater Be sure to provide all pertinent facts when you call or visit Selling prices will be furnished on request or parts will be shipped at prevailing prices and you will be billed accordingly The model number of your Wat...

Page 24: ...talled for indoor operation only used at temperatures not exceeding the maximum calibrated setting of its thermostat used at water pressure not exceeding the working pressure shown on the heater filled with potable water free to circulate at all times and with the tank free of damaging water sediment or scale deposits used in a non corrosive and non contaminated atmosphere used with factory approv...

Page 25: ...r where to call or contact State Water Heaters 500 Tennessee Waltz Parkway Ashland City TN 37015 phone 1 800 821 2017 The warrantor will only honor replacement with identical or similar water heater or parts thereof which are manufactured or distributed by the warrantor Dealer replacements are made subject to in warranty validation by warrantor PROOF OF PURCHASE AND PROOF OF INSTALLATION DATE ARE ...

Page 26: ...__________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ _____________________________________...

Page 27: ...__________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ _____________________________________...

Page 28: ...28 500 Tennessee Waltz Parkway Ashland City TN 37015 www statewaterheaters com ...

Reviews: