Maglink 16T rev.08 2015-07 - ENG
21
For correct working please select Connection mode ONLINE.
For each tank user must set appropriate parameters.
Tank
it is possible to select from 1 to 16 available tanks.
Description
Description of the tank name which will appear on the display, for example: Diesel
Address
Unique serial number written on the probe head.
Product
select product type contained into the tank where has been installed the level sensor referred to the S.N. selected on
the channel.
Tot. capacity
Total capacity in liters/gallons of the tank, data provided by the tank strapping table.
Tank Height:
height of tanks in mm/inches, data provided by the tank strapping table.
Offset:
Offset product float (-30000 +30000 mm): value shown in mm with ±1mm resolution to align the measure of the
product float’s height.
Zero Water
Offset water float (30000 mm): value shown in mm with 1 mm resolution with an absolute value below which the
reading of the water float’s height is zero.
IFSF – Product Nb numeric code (max 8 digits) used to identify the product
ID/SN DVD and DVD Offset: for future use.
Summary of Contents for MAGLINK 16T
Page 1: ...INSTALLATION MANUAL CONSOLE MAGLINK 16T...
Page 3: ...Maglink 16T rev 08 2015 07 ENG 3 30 07 15 8 GENERAL REVISION 11 X X...
Page 29: ...Maglink 16T rev 08 2015 07 ENG 29...
Page 43: ...Maglink 16T rev 08 2015 07 ENG 43 CERTIFICATION...
Page 44: ...Maglink 16T rev 08 2015 07 ENG 44...
Page 45: ...Maglink 16T rev 08 2015 07 ENG 45...
Page 46: ...Maglink 16T rev 08 2015 07 ENG 46...
Page 47: ...Maglink 16T rev 08 2015 07 ENG 47 NOTIFICATION...