1-3.2.40

FIGURE 3

NOMINAL WETTING PATTERN

AT MINIMUM REQUIRED FLOW CONDITION

FOR 20’ x 20’ COVERAGE AREA

FIGURE 4

#4947 SPRINKLER SOCKET

#4948 WRENCH & SOCKET COMBINATION

FIGURE 5

#4300 PROTECTIVE CAP REMOVAL TOOL

DRIVE

3/8" SOCKET

ACCEPTS

WRENCH

RECESS

WRENCH

COMBINATION

WRENCH & SOCKET

#4948

#4947

SOCKET

8'

6'

4'

0'

2'

8'

6'

4'

0'

2'

10'

8'

6'

4'

2'

8'

6'

4'

2'

20' x 20' Coverage Area

19 GPM

Horizontal

Minimum Vertical

Distance from

Clearance

Sprinkler to

Below

Obstruction

Sprinkler

Below Sprinkler

Heat Collector,

Heat Collector, ft.

in.

More than 6.0

24

From 3.0 to 6.0

19

Between 2.0 and 3.0

16

From 1.0 to 2.0

13

Less than 1.0

10

TABLE C

MINIMUM VERTICAL CLEARANCE BETWEEN

TOP OF FREE STANDING OBSTRUCTION AND

SPRINKLER HEAT COLLECTOR

Horizontal

Maximum

Distance from

Vertical

Sprinkler to

Clearance

Obstruction

Below

Below Sprinkler

Sprinkler

Deflector, ft.

Heat Collector, in.

Less than 0.5

Not Permitted

0.5 to less than 1.0

0

1.0 to less than 2.0

1

2.0 to less than 2.5

2

2.5 to less than 3.0

3

3.0 to less than 3.5

4

3.5 to less than 4.0

6

4.0 to less than 4.5

7

4.5 to less than 5.0

9

5.0 to less than 5.5

11

5.5 to less than 6.0

14

TABLE B

MAXIMUM VERTICAL DISTANCE

FROM SPRINKLER HEAT COLLECTOR

TO BOTTOM OF CEILING OBSTRUCTION