SPS5.1 Manual

4

Delay Time

                   

This is a user-settable start delay time in the range 0 to 99 hours 59 mins.  This feature can be used to
delay firing - enabling firing during the night, possibly on low-tariff electricity.

Ramp 1

             

Heating is performed to increase the temperature of the load from ambient to temperature t1.  The value
of t1 is user-settable in the range 0-1310°C.  The rate of increase of temperature depends on the ramp
rate selected.  This ramp rate is user-settable in the range 20-240°C/hour.

Ramp 2

             

Heating is performed at full power (100% energy) to increase the temperature of the load from
temperature t1 to the soak temperature.  The soak temperature is user-settable in the range 0-1310°C.

Soak Time

                  
This is the time that the controller dwells at the soak temperature.  The soak time is user-settable in the
range 0 to 99hr 59mins.  After soaking the controller cuts off heating power and the load is allowed to
cool naturally.

2.3

Keys

Pressing this key when 

READY 

is displayed will start a firing using firing parameters

which have been previously selected with the 

SET

 key.  Pressing this key when a firing in

in progress will immediately abort the firing.

Pressing this key when 

READY 

is displayed enables the user to select firing parameters.

Pressing this key during a firing has no effect.

This is used to increment user input when in SET mode.  Pressing this key has no effect
when 

READY 

is displayed or when a firing is in progress.

This is used for digit select when in SET mode.  It is also used to review controller
status during firing.  Pressing this key when 

READY 

is displayed has no effect.

RUN

HALT

SET

SPS5.1 Manual

       Page 9

3.4

Wiring

Relay

K1 K2 K3 L  N  E

2

1

1

N

Contactor

Thermocouple
Connections

+

-

+

SK2

6

Contactor coil
suppressor
(must be fitted)

N

E

L

SK1

L N E

3.4.1

Contactor Coil Suppression

                                            

The coil of the contactor 

must be suppressed

 with an RC filter network.  The RC network must

be connected directly across the coil terminals on the contactor.

Suitable proprietary RC filter networks fitted with insulated wire leads are:-

1.

RS Components

Part No. 210-364

2.

RS Components (tab fixing)

Part No. 210-370

3.

Farnell Electronic Components

Part No. 218-893

Note

        
to ensure compliance with the
EMC & LVD Directives lead
lengths should not exceed 3m.

Summary of Contents for SPS5.1

Page 1: ...oller RUN HALT SET SPS 5 1 Stanton Pottery Supplies Ltd Canal Lane Westport Lake Tunstall STOKE ON TRENT Staffordshire England ST6 4NZ Tel 44 0 1782 835467 Fax 44 0 1782 812435 email sales stanton kilns co uk www stanton kilns co uk Issue 5 1E01 Date 10 July 98 Stanton Pottery Supplies Ltd Manufactured in Staffordshire U K ...

Page 2: ... wire size 1 5mm Temperature Ramp Rate to temperature t1 setting Range 20 to 240 C hour Resolution 20 C hour t1 setting Range 0 to 1310ºC Resolution 1ºC t2 setting Trim Range 0 to1310ºC Resolution 1ºC START DELAY setting Range 00 00 to 99hr 59min Resolution 1 min Control Accuracy Reading accuracy 0 25 FSD 1 digit P I D Control Cold junction compensation Environmental Operating temperature range 0 ...

Page 3: ...is switched off and an error message is displayed for one minute After this period the controller resets itself and restarts as if a power failure had occurred If the potential error has cleared the instrument will proceed as normal If the error condition persists the instrument will repeat the error display cycle In the event of an error contact the supplier quoting the error number THERMOCOUPLE ...

Page 4: ...rs which have been previously selected with the SET key Pressing this key when a firing in in progress will immediately abort the firing Pressing this key when READY is displayed enables the user to select firing parameters Pressing this key during a firing has no effect This is used to increment user input when in SET mode Pressing this key has no effect when READY is displayed or when a firing i...

Page 5: ...S5 1 K4 is Mains Live input K5 is Mains Neutral input K6 is Earth input an Earth must be fitted to this controller VR1 is the display contrast control FS1 is the protective fuse 1 0A Anti surge Wickmann type TR5 T1A 250V Farnell Electronic Components 150 988 RS Components 226 6583 SPS5 1 Manual Page 5 2 4 Setting Pressing the SET key when READY is displayed causes the cur rently selected ramp rate...

Page 6: ...actions to avoid a firing being aborted The instrument has no direct knowledge of how long the power has been off so the recovery action taken depends on where the instrument had reached in the firing sequence prior to power failure as detailed below Before Power Failure After Power Failure In READY mode Timing delayed start On Ramp 1 approaching t1 On Ramp 2 approaching t2 In Soak Period timing S...