9
Test
Action
Observation
Controller
Reader
Reader and
Request to Exit
Test
Present a key to each
reader - the lock will
activate.
The door green LED flashes
once for SIGA, twice for
SIGB.
The reader LED
flashes once for
SIGA, twice for SIGB.
Press the
Request to
Exit
switch - the lock will
activate.
The door green LED flashes
three times and the yellow
LED is lit.
The reader LED
flashes three times.
Open the door contact.
The door green LED flashes
four times and the red LED
is lit.
The reader LED
flashes four times.
Auxiliary and
Lock Relays
Test
Present a key to a reader, press the
Request to Exit
switch and open the
door contact simultaneously.
The appropriate auxiliary relay is activated.
Remove link to
0V
on tamper or open
circuit tamper switch.
Both auxiliary relays are activated.
Remove link to
0V
on emergency
override or leave open circuit tamper
switch.
The auxiliary relay is activated.