background image

Especially Airtight Properties:-

If the stove is being fitted in a property where the
design air permeability is less than 5m

3

/ (h.m

2

) (nor-

mally newer properties built from 2006), then a per-
manent ventilation must be fitted to provide 550mm

2

of ventilation for each kW of rated output.  

10

Where such an installation exists, a test for spillage
should be made with the fan or fans and other appli-
ances using air in operation at full rate, (i.e.extrac-
tion fans, tumble dryers) with all external doors and
windows closed. 
If spillage occurs following the above operation, an
additional air vent of sufficient size to prevent this
occurrence should be installed.

If a draught stabiliser is also fitted then the require-
ment is 850mm

2

per kW of rated output.  

It is recommended to bring the air supply for the
stove into the house using a 4” plastic pipe.  Where
the pipe meets the outside wall make sure a vent
cover is fitted properly to ensure no rodents can
enter via the vent pipe. 

The vent pipe should be located to prevent the
ingress of moisture and in a location where it will not
get blocked with leaves or any other debris.  As wind
effects can create suction and pressure zones of 

opposite sides of the dwelling it is recommended to
run the air vent from opposite poles (North, South, 
East & West) of the dwelling and tee off for the air
supply to the stove.  This should negate the effect 
of suction and pressure zones.  See Fig. 7

‘HETAS product approval covers this appliance
when installed in accordance with the manufactur-
er’s instructions and relevant standards. As there is
currently no standard for Ducted Combustion Air
Supply this does not fall within the remit for HETAS
product approval. Responsibility for the specification
of this and for appropriate manufacturer’s instruc-
tions is carried by the appliance manufacturer, as
allowed for under the Building Regulations.’

Note:  When Installing
outside air pipe must
adhere to ‘Clearance
t o C o m b u s t i b l e ’
Section.

Fig.7

HEAT RECOVERY VENTILATION

Where a stove is to be installed in a dwelling with

Heat Recovery Ventilation

(HRV) a number of

precautionary measures must be undertaken:

Should for example the delivery fan in the HRV unit
fail and the extraction fan in HRV fan continue to
run the HRV may create a pressure less than
atmospheric, this low pressure will effect the flue
pressure which is required to safely evacuate the
products of combustion from the stove.

1.

Fit an adequately sized vent in the room to pre-
vent pressure less than atmospheric occurring.
The size should be established by closing all 
windows and doors and then creating the 
possible failure situation.  Then open a window
in the room where the stove is fitted, slowly 
until the pressure reaches atmospheric.  The 
size of the window opening should be
measured and a vent of the corresponding size
installed.

2.

Fit a CO Alarm which has been approved to 
EN 50291.

EXTERNAL DUCTED AIR

An outside air kit complete with primary air supply
can be ducted from outside and is available to order
for connection to the stove.

Note:
There must not be an extractor fan fitted in the
same room as the stove as this can cause the
stove to emit smoke and fumes into the room.

Summary of Contents for Oisin

Page 1: ...ld be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the boiler stove in situations where chil...

Page 2: ...ion HRV 10 14 Location 11 15 Clearance to Combustibles 11 16 Floor Protection 11 17 Plumbing 12 18 Water Pipe Locations 12 19 DHW System Domestic Hot Water 12 20 Safety Valve 13 21 Direct Domestic Cyl...

Page 3: ...Chimney Cleaning 16 41 Glass Cleaning 17 42 Vitreous Enamel Cleaning 17 43 Cleaning a Matt Black Senotherm Stove 17 44 Change Rope Seals 17 45 Prolonged Periods of Non Use 17 46 Fire Safety 18 47 Gla...

Page 4: ...lled as per the requirements of the manual Failure to comply with the Installation requirements or Building Regulations will void your warranty Waterford Stanley reserve the right to replace any part...

Page 5: ...g Regulations to have a carbon monoxide alarm fitted to any room with a solid fuel appliance Location 10 Clearance to combustible materials must be adhered to as described in the Clearance to Combusti...

Page 6: ...allow a build up of ashes in the ash pan as this will cause the grate to burn out prematurely Empty the ashpan when refuelling 7 Avoid slow burning of damp or unseasoned fuel as this will result in t...

Page 7: ...and use appropriate protective equipment Metal Parts When installing or servicing this stove care should be taken to avoid the possibility of personal injury IMPORTANT WARNING This stove must not be i...

Page 8: ...date should be removed before connecting this appliance If con necting to an existing chimney with a flue diameter of more that 8 it is recommend to line the flue using a suitable stainless steel flu...

Page 9: ...o provision for closure The effective free area of any vent should be ascertained before installation The effect of any grills should be allowed for when determining the effective free area of any ven...

Page 10: ...with the manufactur er s instructions and relevant standards As there is currently no standard for Ducted Combustion Air Supply this does not fall within the remit for HETAS product approval Responsi...

Page 11: ...ss through walls or partitions constructed of combustible materials provided the connector is either listed for wall pass through or is routed through a device listed for a wall pass through and is in...

Page 12: ...DEL ONLY The DHW Model must be connected to a gravity system Care should be taken to ensure that the domestic hot water installation is correctly installed and that it complies with all relevant codes...

Page 13: ...ndirect cylinder fixed in an upright position recommended for hot water storage and it should be connected to the boiler by 28mm diame ter flow and return piping The pipes should not exceed 7 8 meters...

Page 14: ...t and burn rate rotate the spin valve clockwise until fully closed You will soon learn spin valve settings to best suit your requirements See Fig 16 Fig 16 Note The controls may become hot when the st...

Page 15: ...ing checks described previously have been carried out correctly and that the chimney has been swept clean is sound and free from any obstructions As part of the stoves commissioning and handover the i...

Page 16: ...RHS of the baffle can pass below the fixing rib on the RHS panel thus allowing the baffle drop into the firebox and be removed from the stove lf the baffle is distorted can t be removed as described a...

Page 17: ...cleaned when cool and cleaned with a non abrasive cloth using warm soapy water For stubborn deposits a grade 0 steel wool can be used whilst tak ng care not to scratch the glass with any coal ash dep...

Page 18: ...c turers instructions Provision of an alarm must not be considered a substitute for either installing the appliance correctly or ensuring regular servicing and maintenance of the appliance and chimney...

Page 19: ...XX 16 BACK BRICK H00002AXX 17 SERIAL NUMBER PLATE N00234BXX 18 DATA PLAQUE N00440AXX 19 GRATE SUPPORT PLATE Q00001BXX 20 TOP BAFFLE Q00003AXX 22 FIRE FENCE Q00005AXX 23 FIRE FENCE RETAINER Q00006AXX 2...

Page 20: ...Rev 008 YS 280417 Item No N00002AXX 20 Manufactured by Waterford Stanley Ltd Unit 401 403 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315...

Reviews: