Connecting Breakout Status Signal Wiring (Magic-Force Operators)
WARNING
To prevent injury to personnel and damage to equipment, control box power must be deenergized before
connecting breakout status signal wiring.
CAUTION
If the motor is running and the breakout status switch is
not
connected, arcing across the breakout switch
contacts can occur. This will result in damage to the breakout switch. To prevent damage from switch
contact arcing, the breakout status switch must
always
be connected.
3.4.1
DISCONNECT power pigtail assembly.
3.4.2
IF single-operator application, PERFORM the following:
•
INSTALL one breakout status switch wire (yellow) to terminal 6 of control box
connector TB1.
•
INSTALL second breakout status switch wire (yellow) to terminal 8 of control
box connector TB1.
3.4.3
IF dual-operator application, PERFORM the following:
•
INSTALL one breakout status switch wire (yellow) from one operator to terminal
6 of control box connector TB1.
•
INSTALL one breakout status switch wire (yellow) from second operator to
terminal 8 of control box connector TB1.
•
CONNECT remaining two yellow breakout status switch wires together with a
wire nut.
3.4.4
VERIFY breakout status/breakout cams are properly set as follows: