Temperature transmitter Ex i
Series 9182
DIP switch settings
*) Default setting upon delivery
**) see Section 8.3.2.
0 = OFF
1 = ON
12-pole DIP switch
(lateral)
4-pole DIP switch
(at the front)
Switch "S2"
12 11 10 9 8 7 6 5 4 3 2 1 LF1 ADJ1 LF2 ADJ2
PC programming *)
0
0
0
0 0 0 0 0 0 0 0 0 x
x
x
x
Line fault detection
Channel 1: OFF
0*)
Channel 1: ON
1
Channel 2: OFF
0*)
Channel 2: ON
1
Output
0 to 20 mA
0
4 to 20 mA
1
Ex i Input
Pt100:
2-wire **)
Adjustment possible
0
0 0 0
0
0
without adjustment
1
0 0 0
0
0
3-wire
1
0 0 0
1
0
4-wire
1
0 0 0
0
1
Thermocouple:
E
0 0 1
Type E
0 1 0
Type J
0 1 1
Type K
1 0 0
Type N
1 0 1
Type R
1 1 0
Type T
1 1 1
Reference junction
Reserved
0
External
1
Measuring range
See the following table