Operation
28
260520 / 640960300090
2018-11-08·BA00·III·en·02
Emergency Luminaire with LED
Series EXLUX 6409/1
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
During emergeny light operation
The LED indicator is switched off.
LED indicator State
Description
Green
Luminaire is ready for
operation
Blinking green Luminaire is ready for
operation
Function and rated operating time test
activated
Red
Error
Battery is defective or electric circuit is
interrupted
Blinking red
Error
Last function and/or rated operating time test
faulty
Flashing red
Error
LEDs defective
Blinking
green/red
Luminaire is ready for
operation No emergen
-
cy light operation
Emergency light operation is deactivated by
remote switch
Flashing
green/red
Luminaire is ready for
operation
Reset signal detected