Compact Luminaire with LED
Series C-Lux 6102/1, Series C-Lux 6109/1
Emergency light blocking
A remote switch for emergency light blocking can be connected via terminals 6 and 7
at the control gear.
20716E00
8.3
Function and rated operating time test (series 6109/1 only)
To carry out the test, the following prerequisites must be fulfilled:
• the time interval has expired.
• the power supply operation was active for at least 1 hour.
• the remote switch is closed.
The test result is shown on the LED indicator.
During a test the luminaire is switched on.
Function test
• starts within 24 hours after commissioning.
• is carried out every 7 days.
• takes 1 minute.
• checks the function of the LEDs and the battery.
Rated operating time test
• starts within 44 days after commissioning.
• is carried out once a year.
• checks the function and the operating time of the luminaire during emergency light mode.
• is repeated after 14 days if rated operating time test is faulty.
Remote switch is closed
Remote switch is opened
Power supply
operation
Switching on the luminaire
depending on operation mode
Switching on the luminaire
depending on operation mode
Power failure
Emergency light function
No emergency light function
L
L‘
BAT+
2
3
4
5
6
7
N
BAT-
Remote Switch