CPU module for Zone 2
Series 9442/35
6.3.1 Connecting the fieldbus
19635E00
Connect the primary fieldbus conductor with Sub-D plug to the X1 Sub-D socket.
Secure Sub-D connector against loosening using screws. Tightening torque of
0.5 to 0.6 Nm.
Secure the connection line against tensile load and scuffing.
The shielding of the fieldbus must at least be connected at the point with the equipotential
bonding.
6.3.2 Connect Ethernet
19636E00
Connect the primary Ethernet line with locking hook on the standard RJ45 plug connector
to the X2P1 RJ45 socket until it audibly engages.
Connect the secondary Ethernet line with locking hook on the standard RJ45 plug
connector to the X2P2 RJ45 socket until it audibly engages.
Secure connection lines against tensile load and scuffing.
The shielding of the Ethernet line must at least be connected at the point with
the equipotential bonding.