Parameterization and commissioning
15
CPU & Power Module for Zone 2 / Div. 2
Series 9440/15
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
9.1
Parameterizations
Parameterization and commissioning of the CPM and of the connected I/O modules is
carried out using the automation system and the ServiceBus (optional).
Only the fieldbus address of the CPM must be set directly at the module.
The buttons of the LCD display can be used
• to set the fieldbus address of the device
• to display information about the CPU & Power Module and the I/O modules installed
on the BusRail (see chapter "Display").
9.1.1 Start-up
9.1.2 Setting the fieldbus address
Display
Settings
12258E00
• After connecting the auxiliary power, the device will boot.
• After successful completion of the booting process, the LCD
display switches to the system level (shown on the left).
The fieldbus address can be set only if the device is not in the Data Exchange
mode.
Display
Settings
12258E00
• Initial display (shown on the left)
12259E00
• Press ▲ and ▼ simultaneously.
The following display appears (shown on the left).
12260E00
• Press ▲ and ▼ simultaneously.
The following display appears (shown on the left).
12261E00
• Press ▲ and ▼ simultaneously.
The following display appears (shown on the left).
• Press ▲ or ▼ until the desired fieldbus address has been set.
When pressing the button continuously the value changes
rapidly. The setting range goes from 0 to 127.
12262E00
• Press ▲ and ▼ simultaneously.
The following display appears (shown on the left).
12263E00
• Press ▲ and ▼ simultaneously. The settings are applied.
The device boots again. Or
• Press ▲ or ▼ . The following display appears
(shown on the left).
• Press ▲ and ▼ simultaneously. The setting procedure is
cancelled.
FBAdr
FB
I/O
5
OK
OK
FBAdr
FB
I/O
5
OK
OK
CPM
active
9440/15-01-11
CPM
active
FB addr :
5
set FB address
select:
5
accept changes ?
yes -> CPM reset
accept changes ?
No