Technical data
10
162278 / 9440609310
201
9
-0
1
-10·BA00·III·en·0
7
CPU & Power Module for Zone 2 / Div. 2
Series 9440/15
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
For further technical data, see
r-
stahl.com.
Power supply for the I/O
modules via the BusRail
Voltage range
22.5 ... 26.2 V DC
Max. current
4 A
Max. number
I/O modules
16
Redundant supply of
the I/O modules
yes
Undervoltage
monitoring
yes
Galvanic separation
between power supply
and system
components
1500 V AC
between Fieldbus/
ServiceBus interface
and system
components
1500 V AC
between two bus
interfaces
500 V AC
Ambient conditions
Ambient temperature
-20 ... +65 °C
Storage temperature
-40 ... +70 °C
Relative humidity
(no condensation)
< 95 %
Use at the height of
< 2000 m
Sinusoidal vibration
(IEC EN 60068-2-6)
1 g in frequency range between 10 ... 500 Hz
2 g in frequency range 45 ... 100 Hz
Semi-sinusoidal shock
(IEC EN 60068-2-27)
15 g (3 shocks per axis and direction)
Electromagnetic
compatibility
Tested according to the following standards and regulations:
EN 61326-1, EN 61000-4-1...6, NAMUR NE 21
Observe the "Cabinet installation guide"
Mechanical data
Connection
Fieldbus RS 485
Sub-D socket 9-pin
ServiceBus RS 485
Sub-D socket 9-pin
Power supply
Plug-in screw terminals to 4.0 mm
2
/ 12 AWG
Module enclosure
Polyamide 6GF
Fire resistance (UL 94)
V2
Degree of protection
(IEC 60529)
Modules
IP30
Connections
IP20
Mounting / Installation
Installation conditions
Mounting type
on 35 mm DIN rail NS 35/15
Mounting orientation
horizontal and vertical