Installation
7
Wall-mounting socket/Coupler
8575/13/8575/14
Connections for wall-mounting socket 8575/13:
X
Open connection area cover.
X
Push cable through cable gland and into connection area.
X
Remove insulation from cable (max. 4 mm
2
) ends.
X
Fit stripped cable ends to appropriate terminal slots in socket flange and tighten clamp.
When tightening clamp, ensure stripped ends of cable are fully underneath the clamps.
X
Adjust cable so that terminals are not under tension. Fully tighten cable gland screw
cap. Carefully replace connection area cover and tighten all screws.
Connections for coupler 8575/14:
X
Loosen four enclosure screws and remove socket flange. Loosen pressure screw
clamp and remove pressure screw. Remove pressure ring and gasket from cable
gland.
X
Push the cable through pressure screw, pressure ring and gasket. If necessary,
increase gasket internal diameter by trimming it to match the cable. Push cable into
enclosure through cable gland.
X
Remove insulation from cable (max. 4 mm
2
) ends.
X
Fit stripped cable ends to appropriate terminal slots in socket flange and tighten clamp.
When tightening clamp, ensure stripped ends of cable are fully underneath the clamp.
X
Adjust cable so that terminals are not under tension. Fix cable in tension reliever.
Carefully reassemble enclosure and replace screws. Press gasket and pressure ring
into cable gland and fully tighten pressure screw. Align pressure screw and fix terminal
clamp.
Earth connection:
An earth connection must be made in all circumstances. Plugs and sockets for extra-low
voltages have no earth contact.
09197T00
09290T00
a = 60 mm
b = 9 mm
)
When terminal sleeves are fitted, they must be gas-tight and applied with a
suitable tool.