Mounting
6
8575618300
S-BA-8575/13/14-01-en-11/04/2007
Wall-mounting socket/Coupler
8575/13/8575/14
7
Mounting
The type 8575/13 wall-mounting socket must be fixed vertically with four screws on a flat
wall. (For fixing dimensions, see sketch above or back of socket itself.)
The fixing holes are elongated. This permits vertical and horizontal adjustment during
mounting.
When a wall-mounting socket 8575/13 or coupler 8575/14 is installed in the open, it is
advisable to provide a protective cover or wall.
Transport and storage are permitted only in the original packaging.
8
Installation
Mains connection
:
X
The conductors must be carefully connected.
X
The conductor insulation must reach to the terminal. The conductor itself must not be
damaged (nicked) when removing the insulation.
X
Ensure that the maximum permissible conductor temperatures are not exceeded by
suitable selection of cables and means of running them.
Please also refer to the terminal details under Technical Data.
)
The extra-low voltage plugs and sockets have no earth contact. To ensure
correct insertion, a primary key is provided on the socket collar. A secondary
key on the socket collar is located at different clock positions to define the
voltage and frequency of the particular plug and socket assembly.
WARNING
Please consult the manufacturer if operating conditions are non-standard.
Dimension drawings
(all dimensions in mm) - subject to alterations
04509E00
03209E00
8575/13
8575/14
Wall-mounting socket type 8575/13 mounting position:
Flap cover facing downwards, connection area at the top
Coupler type 8575/14 position for use:
Suspended by clip ring
)
If no clean and dry surface is available on which to position the coupler, then
a suitable attachment point for the clip ring must be found.