8570601300
S-BA-8570/11/12-03-en-31/01/2007
Installation
11
Wall-Mounted Socket, Plug
8570/11, 8570/12
Installing auxiliary contacts
11202E00
X
Open the casing.
X
Pass the cable through the cable entry into the connection chamber.
X
Open the screwless clamps, using a screwdriver (2)
(blade 06 x 3.5, shape A, in accordance with DIN 5262 or ISO 2380-1 respectively).
X
Insert the conductors into the corresponding screwless terminals and clamp them (3).
The stripped ends of the wire must be fully within the terminal clamp.
X
Align the wires (clamped ends must be relieved of strain).
X
Tighten the cable entry gland(s).
X
Close the casing (tightening torque: see Chapter 5, “Technical Data“).
8.2 Installation, plug, type 8570/12-...
11222E00
X
Screw the cable gland (1) off and remove the dust exclusion plate (2).
X
Remove the pressure ring (3) and seal (4).
X
Remove the shell securing screws (5) and remove the plug shell (6).
X
Insert the cable (max. 4 mm
2
) through the cable gland (1), pressure ring (3) and
seal (4). If necessary, cut the seal out to match the cable diameter.
X
Open the strain relief (7) and swivel it by 90°.
X
Insert the conductors into the corresponding terminals and clamp them (max. 1.2 Nm).
X
The stripped ends of the wire must be fully within the terminal clamp.