Installation
9
Residual current circuit-breaker with
integral overcurrent protection 8562/5
8
Installation
8.1 Mains connection
8.2 Rated connection cross-section
Single-wire, stranded or flexible stranded copper conductors may be used. 1 or 2 cables
may be connected to a single terminal. If the conductors are single-wire, both must have
the same cross-section and be of the same material. No special preparation is required
prior to making the connections.
Connect the cables with particular care.
Choose suitable cables and route them accordingly to ensure that the maximum
permissible conductor temperatures are not exceeded.
To ensure that creepage distances are maintained remove precisely 10 or 17 mm of
insulation.
The conductor must not be damaged (scored) when stripping the insulation!
Only heat-resistant cables must be used, if connected directly.
)
When terminal sleeves are fitted, they must be gas-tight and applied with a suitable tool.
Conductor
Main contact terminals
Auxiliary contact terminals
single-wire
2 x 1.5 ... 10 mm
2
*
2 x AWG 16 to 8
04935T00
2 x 0.75 ... 2.5 mm
2
2 x AWG 18 to 13
04937T00
1 x 10 mm
2
(bend the end of the
conductor)
04938T00
04939T00
stranded or
flexible-stranded
2 x 1.5 ... 6 mm
2
2 x AWG 16 to 10
04940T00
2 x 0.75 ... 1.5 mm
2
2 x AWG 18 to 16
04941T00
Permissible tightening
torques for the options
mentioned*
1.8 ... 2.0 Nm
16 ... 18 lb.in
1.0 ... 1.2 Nm
9 ... 11 lb.in
*Permissible tightening
torques for 10 mm
2
single-
wire cable
2.5 Nm
23 lb.in