Technical data
6
8562606300
S-BA-8562-02-en-24/08/2007
Residual current circuit-breaker with
integral overcurrent protection 8562/5
Rated switching capacities
Breaking capacity
6 kA resp. 10 kA 2-pole; 10 kA 1-pole + N (25 kA to IEC)
Version
Type A, pulse current sensitive to EN 61008
Characteristics
Back-up fuse
Operating temperature range
-20 °C ... +40 °C
Material
Housing
Epoxy resin
Auxiliary contacts
Version
Options: 1 CO or/and 1 CO as a fault indication contact.1 NO and 1 NO as a fault indication
contact.
Rated working voltage
max. 230 V, AC
Rated working current
5 A, at 230 V, AC
1 A at 60 V, DC
Terminals
1,5 mm
2
clamp terminals
Poles
Series with 6 kA
Series with 10 kA
Voltage
(V)
Current
(kA)
Voltage
(V)
Current
(kA)
AC to EN 60898
1 - 2
I
cn
/
I
cs
230 / 240
6
I
cn
230 / 240
10
AC toEN 60947-2
1
I
cu
240
10
I
cu
240
15
1+N,
2
I
cu
127
30
I
cu
127
40
240
20
240
30
415
10
415
15
DC to EN 60947-2
(Time constante
15 ms)
1
I
cu
/
I
cs
60
20
I
cu
/
I
cs
60
25
2
125
25
125
30
Characteristic
to EN 60898
B
C
Rated current range
6 A ... 32 A
0,5 A ... 32 A
Loads
> Elektric heatings
> Lighting
> Socket outlet
circuits
> Control circuits
e.t.c.
> Operating equipment
> Light fitting groups
> Motors
> Transformers
e.t.c.
Normal temperature
30
o
C
30
o
C
Thermal overload trip
1,13 ... 1,45 I
n
1,13 ... 1,45 I
n
Magnetic trip
3 ... 5 I
n
3 ... 10I
n
Back-up protection with preceding fuse
Following miniature circuit-
breaker
Preceding fuse type gG
Tripping characteristic
C
B
B, C
Type
Rated current I
N
[A]
min. rated current
[A]
max. rated current
[A]
8562/5
1
4
-
2
8
63
3
10
6
20
10
80
10
25
16
16
40
20
20
50
32
100
25
63
40
32
80
50