Technical data
4
8562606300
S-BA-8562-02-en-24/08/2007
Residual current circuit-breaker with
integral overcurrent protection 8562/5
6
Technical data
Explosion protection
E
II 2 G EEx de IIC
E
I M 2 EEx de I
Certificates
PTB 02 ATEX 1049 U
Gas explosion protection
(IECEx)
Ex de IIC
Ex de I
IECEx certification
IECEx PTB 06.0062U
No. of poles
1-pole + N; 2-pole
Rated working voltage
127 V ... 230 V, AC
Minimal Voltage U
bmin
Maximal Voltage U
bmax
255 V AC
Rated operating frequency
50 Hz / 60 Hz
Rated isolation voltage
500 V
Rated working and
leakage currents
Tripping time at rated
tesidual current
< 40 ms
Impact strength
250 A, 8 / 20
m
s
Life
mechanical
10
5
switching cycles
electrical
10
5
switching cycles
Terminals
Isolation function
yes
Pulse resistance
6 kV
Utilisation category
A (acc. to EN 60947-2)
1-pole + N:
100 V AC
2-pole:
127 V AC
1-pole + N (54 mm):
IN = 6 A ... 16 A; I
∆
N = 10 mA
IN = 6 A ... 32 A; I
∆
N = 30/300 mA
2-pole (99 mm):
IN = 6 A ... 32 A; I
∆
N = 30/300 mA
Main contacts
1.5 ... 10 mm
2
clamp terminals
Auxilliary contacts
1.5 mm
2
clamp terminals