213859 / 825260300060
2019-08-07·BA00·III·en·05
Installation
9
Terminal Box Ex d
8252/1
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Connecting the protective conductor with cable lug:
- Fasten washer (2), protective conductor with cable lug (3), screw locking (4) to the
thread in the enclosure (1) with the screw (5).
- Tighten the screw (5) (tightening torque 2.8 Nm)
- Run and fix the cable near the enclosure to prevent loosening of the cable.
11.3 Internal wiring
11.4 Electrical Connection
- Open the enclosure.
- The conductor must be carefully connected.
- Make sure that the conductor insulation reaches right up to the terminal.
- Do not damage (nick) the conductor when stripping the insulation.
- Ensure that the maximum permissible conductor temperatures are not exceeded by
suitable cable selection and layout.
- Observe the data of the terminal manufacturer.
- Carefully close the enclosure after completing the work.
06817E00
1 = Thread (M6) in the enclosure
2 = Washer
3 = Protective conductor with cable
lug
4 = Screw locking
5 = Screw (M6)
WARNING
If cables and lines are damaged, explosion protection is no longer
guaranteed!
Run cables and lines such that they do not become bent or chafed through
during operation.
2
3
5
1
4