03. ELECTRICAL CONNECTION
ü
Make connections with power supply disconnected.
ü
Check that the power supply does not depend from electrical circuits for lighting.
ü
Always connect the motor to the grounding system (yellow/green).
ü
The supply line must be equipped with a circuit breaker. The supply line must be fitted with a device
with a voltage category III, i.e. the distance between the contacts must be of 3,5 mm at least.
ü
The product doesn’t not provide any protection against overloads or short circuits. Provide the supply
line with an adequate protection to the load, for example a fuse of maximum value 500 mA.
ü
The section of the connecting cables must be proportionate to their length and to the absorption of the
load, and in any case not less than 1,5 mm.
ü
Once the electrical connections are finished, bring the motor/motors to the intermediate
position and check that in the “wind alarm” condition the module commands the upward
movement to the motor/motors
(to exit form the”wind alarm”, press any buttons P1, P2 or P3).
L (Phase)
N (Neutral)
MAIN POWER
SUPPLY
connector
cable 593.K.XS.00
FUSE 500mA
04. MEMORIZATION/CANCELLATION OF 593.K.XS.00 IN A RECEIVER
The procedure to memorize or delete 593.K.XS.00 in a receiver depends on the receiver, but usually is the following:
- with the transmitter bring the motor/receiver to the intermediate position.
- press PROG on the transmitter (with 594.T.X... in the battery compartment. / with 593.T.X1.00 in the back in the hole) for around 5 seconds to let the
motor/receiver enter into the programming (the motor/receiver makes a signal)
Art. 594.T.X... Art. 593.T.X1.00
- press P1 on 593.K.XS.00 and hold it until the motor/receiver confirmation movement.
To check that the radio sensor is correctly stored on the receiving device, give an up or down command to the receiver: shortly pressing P1 on the radio
sensor, the movement must stop.
brown
blue
P1