Page | 17
08: Programmable outlets setting
Interface
Setting
0-999: setting the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices on
battery mode.
09: Acceptable input voltage range setting
Interface
Setting
For 200/208/220/230/240 VAC models, you may choose the
following selection for acceptable input voltage range:
110/300 flashing in turns: The acceptable input voltage range is
from 110V to 300V.
160/260 flashing in turns: The acceptable input voltage range is
from 160V to 260V.
170/270 flashing in turns: The acceptable input voltage range is
from 170V to 270V.
For 100/110/115/120 VAC models, you may choose the following
selection for acceptable input voltage range:
55/150 flashing in turns: The acceptable input voltage range is from
55V to 150V.
80/130 flashing in turns: The acceptable input voltage range is from
80V to 130V.
85/135 flashing in turns: The acceptable input voltage range is from
85V to 135V.
00: Exit setting