Page | 13
5.7 REPO (Option)
User provided switch circuits are required to activate the REPO. Upon activation, the
REPO function trips Breaker 2 (if closed) and Breaker 3 (if closed), interrupting power to
the load. See Section for REPO installation details
To restart the system after activation of the REPO, make sure that the REPO switch is in
the non-activated state before continuing. Then, use the Startup procedure for the MBS.
This REPO only opens the breakers in the Bypass cabinet. The UPS requires
separate REPO wiring isolated from the Bypass Cabinet REPO wiring. See UPS
Manual
Table 2 - Maintenance Bypass Switch States
Breaker 1 = UPS Input
Breaker 2 = Bypass
Breaker 3 = UPS Output
State Name
Breaker
1
Breaker
2
Breaker
3
Normal
closed
open
closed
Overlap
closed
closed
closed
UPS Unloaded
closed
closed
open
Maintenance
open
closed
open
Load Off
open
open
open
Test UPS
closed
open
open
Test Battery
open
open
closed
Not Allowed
open
closed
closed
5.8 Potential Issues:
MBS will not allow BKR2 to close—
1. Check to see that the UPS is on bypass (SWMB is closed).
2. The UPS controls must be powered (BKR1 and SWBY should be closed).
3. Verify that the backfeed prevention interlock signals were properly wired as part of
the installation and that this wiring has not been damaged.
BKR2 in the MBS trips when power is applied—
1. This is likely due to a procedural error. Note that BKR2 and BKR3 must not be
closed at the same time unless the UPS is powered and the UPS is in bypass mode.
2. It is likely that BKR3 is closed and the backfeed prevention interlock function is
preventing BKR2 from staying closed.
3. Since the UPS is not powered, the signal that indicates that the UPS is in bypass
mode cannot be generated.
4. Open BKR3 and close BKR2. BKR2 should close and stay closed.
5. If power to the UPS is not required, open BKR1.