Page | 10
4.4.3 Switch Settings
Switch "S2" on the Options Control Board (refer to
) is a four position "DIP" switch.
Pushing on the top half of each switch section turns it ON, pushing on the lower half turns
the switch OFF. There are labels on the board to help identify the switch section.
The first section "PLT" enables "Power Loss Trip" (or Manual Restart), and should be OFF
unless you want the Bypass and Inverter Output Breakers to trip on loss of power.
The second section "NCR" enables the Normally Closed REPO input and should be OFF
unless there is a normally closed REPO switch connected.
The third section "OTT" is not implemented and should be turned OFF to avoid confusion.
The fourth section is not used and should be turned OFF to avoid confusion.