6
Voltage:
Voltage at motor must be not more than 10% above or below motor name-
plate rated voltage or motor may overheat, causing overload tripping and re-
duced component life. If voltage is less than 90% or more than 110% of rated
voltage when motor is running at full load, consult power company.
TABLE I - RECOMMENDED WIRING DATA 50 HZ 230V. MOTORS
Dist in Ft. (M) - Service to Motor
Model
Motor
0-100
101-200
201-300
Temp.
No.
H.P.
(0-30)
(31-60)
(61-90)
Rating-°C
5JTAC-A
1/2
14 (2.0)
14 (2.0)
14 (2.0)
75
5JTAD-A
3/4
14 (2.0)
14 (2.0)
14 (2.0)
75
TABLE II - RECOMMENDED CIRCUIT BREAKER SIZES 50 Hz 230V. MOTORS
Model
Motor
Full Load
Branch Circuit Breaker
No.
H.P.
(amps)
Rating (amps)
5JTAC-A
1/2
4.0
15
5JTAD-A
3/4
4.7
15