VENTING: THROUGH COMBUSTIBLES
Note A: Double wall PL vent requires a minimum of three inch (3”) clearance to combustibles
and the use of a listed wall thimble, fire stop or roof flashing where applicable.
ATTENTION: We strongly recommend using a battery backup system if the pellet stove is
installed using horizontal venting only. This prevents any smoke from entering your home
in the event of a power failure.
Legend for Figures 2 through 5
A. 45 degree elbow
I. PL Vent Fire Stop
B. Thimble
J. Roof Flashing
C. PL Vent Section
K. Storm Collar
D. Stove Exhaust Pipe
L. Rain Cap
E. Air Intake Damper
M. Outside Air Pipe
F. Air Vent Damper
N. PL Vent Section
G. 90 degree elbow
O. Wall Band
H. 45 degree elbow
P. Outside Air Inlet Cover
1. PL vent may be installed directly through a combustible wall, ceiling or roof according to PL
vent manufacturer’s instructions. (See Figures 2 and 3).
2. The PL vent system must be properly sealed and secured as per PL vent manufacturer’s
specifications. An air tight seal is necessary in connecting the vent to the stove. Using a PL
Vent pipe adapter, secure the PL vent with at least three sheet metal screws and high tempera-
ture silicone adhesive, (RTV), or metal tape at each joint.
Figure 2
Figure3
Corner Installation
Through the Wall Installation
11
Summary of Contents for York Insert
Page 11: ...York Insert Dimensions 10 ...
Page 27: ......