6 .2 LED display, flashing codes, clocking diagnosis output
Color
Function
Diagnosis
output Pin 5
Possible cause
Possible remedy
Green
Safe sensor function
On
OSSD input circuit available,
Door closed
Flashes
1 x
Door opened
Clock 1
Flashes
2 x
OSSD input circuit not available
Door closed
Clock 2
- one previous door in the circuit open
- Wiring error
- Cable interruption
- Close all doors
- at pin 2 and pin 6 +24 V
- or connect the output signals of the previous process
guard locking
Flashes
4 x
OSSD input circuit not available
Door opened
Clock 22
- Door and one of the previous doors are opened
- Wiring error
- Cable interruption
- Close all doors
- at pin 2 and pin 6 +24 V
- or connect the output signals of the previous process
guard locking
Blue
Guard locking function
off
Magnet not actuated
on
Door closed, locking force available
Flashes
1 x
Door closed,
Locking force not reached
- Unit soiled
- Alignment of the anchor plate not correct
- Incorrect calibration
- Clean HOLDX and the anchor plate
- Check alignment of HOLDX to the anchor plate
- Recalibrate with HOLDX Manager
Flashes
2 x
Door opened, magnet actuated
- Magnet actuated and the door opened
- Close the door
Rot
Fault diagnosis
off
No error present
on
Internal device error
Clock 18
- Internal device error
- Switch power supply off and on
- Return to supplier in case of recurrence
Flashes
1 x
Error safety outputs
Cycle 11
- Short circuit between safety outputs, against ground
or a24 V DC
- Switch off the power supply
- Repair the short-circuit at the output
- Apply again the supply voltage
Flashes
2 x
Error safety inputs
Clock 12
- Short circuit between safety inputs, against ground
or a24 V DC
- Only one of the two safety inputs available
- Wire break
- Switch off the power supply
- Repair the short-circuit/wire break at the input
- Apply again the supply voltage
Flashes
3 x
Overvoltage or undervoltage
Clock 13
- The supply voltage was not within the defined limits
- Switch off the power supply
- Ensure the correct power supply and apply the power
supply again
Flashes
4 x
Error door torn opened
Clock 14
- Door was forcibly opened by exceeding the locking force
- Switch power supply off and on
Flashes
5 x
Temperature outside the
Permitted range
Clock 15
- The defined temperature range has been undercut
or exceeded
- Switch off the power supply
- Ensure correct ambient temperature
- Apply again the supply voltage
Flashes
6 x
Wrong RFID actuator
Clock 16
- Incorrect actuator in sensor detection zone
- Use correct actuator
Flashes
8 x
configured B10D - value exceeded
Clock 20
- Value achieved for replacement of connected relay
module (user programmed)
- Check or replace connected relay module.Reset B10D
value
Green
Red
Blue
on
on
on
off
Device start
flashes
2x
flashes
2x
flashes
2x
Clock 19
Teach-in process
only for relearnable version
flashes
1x
flashes
1x
flashes
1x
Clock 21
Teach-in process CAN
Table 2: LED display, flashing codes, clocking diagnosis output