Solar Hybrid Inverter V1.0
24
14
Battery under voltage
alarm point
[14] 44V Default
Battery under-voltage alarm point: when the battery
voltage is lower than such criterion, under-voltage
alarm will be given, the output will not be shut down,
with the Set Range of 40V~52V, Step of
0.4V, available when battery type is user-defined and
lithium battery.
15
Battery Discharge
Limit Voltage
[15] 40V Default
Battery Discharge Limit Voltage: the battery voltage is
lower than such criterion, output
and shut down immediately. Set Range of 40V~52V, Step
of 0.4V, available when the battery type is user-defined
and lithium battery.
16
Equalization charge
[16] DIS
No equalization charging
[16] ENA Default
Enable equalization charging, only Flooded lead-acid
batteries, sealed lead-acid batteries and user-defined
are effective
17
Equalization Voltage
[17] 58V Default
Equalization Charging Voltage, with the Set Range of
48V~58V, Step of 0.4V, available for Flooded lead-acid
battery, sealed lead-acid battery and user-defined
18
Equalization Charging
Time
[18] 120 Default
Equalization Charging Time, with the Set Range of
min~900min, Step of 5min, available for Flooded lead-
acid battery, sealed lead-acid battery and user-defined
19
Equalized Charging
Delay
[19] 120 Default
Equalization Charging Delay, with the Set Range of
min~900min, Step of 5min, available for Flooded lead-
acid battery, sealed lead-acid battery and user-defined
20
Equalization Charge
Interval Time
[20] 30 Default
Equalization Charge Interval Time, 0~30d, Step of 1d,
available for Flooded lead-acid battery, sealed lead-acid
battery and user-defined
21
Equalization Charging
Start-Stop
[21] ENA
Start equalization charging immediately
[21] DIS Default
Stop equalization charging immediately
22
ECO mode
[22] DIS Default
NO ECO mode
[22] ENA
When the ECO mode is enabled, if the load is below 50W,
the inverter output is delayed for 5 minutes and then the
output is turned off. When the hull switch is pressed to
the "OFF" State, and then pressed to the "ON" State, the
inverter will resume the output
23
Overload Automatic
Restart
[23] DIS
Overload automatic restart is disabled. If overload occurs,
the output will be shut down, and the machine will not
be restarted.
[23] ENA Default
Enable overload auto restart. If overload occurs, shut
down output, delay the machine for 3 min and then
restart the output. After 5 times in total, no startup will
be resumed.