SPX FLOW DH-2100 Instruction Manual Download Page 16

16

Determine average outlet flow available by subtracting Aver-

age Purge Flow (APF) found  in 3.6.1.2 from the inlet flow to the
dryer.

NOTE

Average outlet flow may be used to determine available down-

stream air supply if a storage vessel (e.g. receiver tank) of sufficient
volume is available between dryer and point of air usage. Otherwise
use minimum outlet flow to determine downstream air available.

EXAMPLE

Find maximum inlet flow, maximum and average purge flows,

and minimum and average outlet flows for a 60 scfm unit with a MWP
of 150 psig operated at 120 psig on a 10 minute cycle. Dryer will
operate with an inlet air flow of 46 scfm.

Step 1: Find Maximum Inlet Flow @120 psig by multiplying

Maximum Inlet Flow at Rated Conditions from 

Table 3E  by Inlet

Pressure Correction Factor for 120 psig from 

Table 3F : 60 x 1.08 =

64.8 scfm.

Step 2: Find Maximum Purge Flow by multiplying Maximum

Inlet Flow at Rated Conditions from 

Table 3E  by Maximum Purge

Flow Factor from 

Table 3G : 60 x .162 = 9.7 scfm.

  Step 3: Find Average Purge Flow by multiplying Maximum

Inlet Flow at rated conditions from 

Table 3E  by Average Purge/

Repressurization Flow Factor from

 Table 3H:  60 x 0.097 = 5.8 scfm.

NOTE

At  46 scfm inlet flow, dryer is operating at 70% of maximum flow

found in Step 1: (46/64.8 = 70%.) Average purge flow is based on
Economizer Switch setting of 70%.

Step 4: Find Minimum Outlet Flow available by subtracting

Maximum Purge Flow (Step 2) from inlet flow: 46 - 9.7 = 36.3 scfm.

Step 5: Find Average Outlet Flow available by subtracting

Average Purge Flow (Step 3) from inlet flow: 46 - 5.8 = 40.2 scfm.

3.7 Determining outlet pressure dew point at
      various inlet compressed air temperatures:

The outlet pressure dew point is determined by the compressed

air temperature at the inlet to the dryer and cycle time selected ( 4
or 10 minutes). Use 

Table 3I  to determine outlet dew points at var-

ious inlet compressed air temperatures and cycle times.

3.5 Verify that dryer is operating within design
      parameters

3.5.1 Maximum working pressure:
Refer to Serial Number Tag to determine maximum working

pressure of dryer.

WARNING

Do not operate dryer at pressures above the maximum pres-

sure shown on the tag.

3.5.2 Minimum working pressures:
150 psig, 10.5 kgf/cm

2

 MWP models -

60 psig (4.2 kgf/cm

2

) for dryers operated on a 10 minute cycle

80 psig (5.6 kgf/cm

2

) for dryers operated on a 4 minute cycle

250 psig, 17.6 kgf/cm

2

 MWP models

125 psig (8.8 kgf/cm

2

) for dryers operated on a 10 minute cycle

150 psig (10.5 kgf/cm

2

) for dryers operated on a 4 minute cycle.

If lower inlet pressures are encountered, consult factory.
3.5.3 Maximum operating temperature: 120

°

F (49

°

C).

3.5.4 Maximum Inlet Flow Capacity
3.5.4.1 At 100 psig ( 7.0 kgf/cm

2

): For maximum inlet flow at 100

psig (7.0 kgf/cm

2

) refer to 

Table 3E.

3.5.4.2 At pressures other than 100 psig  (7.0 kgf/cm

2

) : Multiply

inlet flow from 

Table 3E  by multiplier from Table 3F  that corresponds

to system pressure at inlet to dryer.

3.6 Determining Purge and Outlet Flows:

3.6.1 Purge Flows
3.6.1.1 Maximum Purge Flow.- Maximum Purge Flow (MFP) is

the amount of purge air flowing through the off-stream tower when
the purge/repressurization valve is open.  After the purge/
repressurization valve closes, the purge flow will gradually decrease
as the off-stream tower repressurizes to line pressure.

For maximum purge flow multiply inlet flow at rated conditions

from

Table 3E by Maximum Purge Flow Factor from Table 3G that

corresponds to the dryer MWP, Cycle Time Setting, and air pressure
at inlet to dryer.  For dryers supplied with the optional Automatic
Purge Saving System operating in the Demand Cycle Mode, use 10
minutes as the cycle time.

3.6.1.2 Average Purge Flow - For dryers with the standard

control board and dryers with the Automatic Purge Saving System
operating in the fixed cycle mode:

The Average Purge Flow (APF) is the actual amount of flow

used during the entire purge/repressurization cycle. It includes the
maximum purge flow (MFP) for a portion of the purge/repressurization
time and the volume of air used for repressurization, averaged over
the cycle time.

To determine average purge flow, multiply maximum inlet flow

at rated conditions from 

Table 3E  by Average Purge/Repressurization

Flow Factor from 

Table 3H  that corresponds to the dryer Maximum

Working Pressure, Inlet Pressure, Cycle Time Setting, and Econo-
mizer Switch Setting.

3.6.2 Outlet Air Flow
3.6.2.1 Minimum Outlet Flow
Determine minimum outlet flow available from dryer by sub-

tracting Maximum Purge Flow (MFP) found in 3.6.1.1 from inlet flow
to the dryer.

3.6.2.2 Average Outlet Flow - For dryers with the standard

control board and dryers with the Automatic Purge Saving System
operating in the fixed cycle mode:

Summary of Contents for DH-2100

Page 1: ...ure containing device Do not exceed maximum operating pressure as shown on equipment serial number tag Make sure equipment is depressurized before working on or disassembling it for service 2 Electric...

Page 2: ...l check points 14 3 3 Shut down 15 3 4 Loss of power 15 3 5 Design parameters 16 3 6 Determining purge and outlet flows 16 3 7 Outlet dew points vs inlet temperatures 16 4 0 MAINTENANCE 18 4 1 Desicca...

Page 3: ...WLY pressurize unit 3 Energize dryer by turning on off switch on I is on O is off 4 Adjust purge air flow rate Turn purge rate valve until Purge Pressure Gauge reads as shown in the following table NO...

Page 4: ...to as the heat of adsorption and is stored in the bed for use during regeneration Desiccant is regenerated by driving off desorbing the water collected on its surface Pressure swing also called heatl...

Page 5: ...me period air inlet switching valve 3B opens and inlet switching valve 3A closes purge and repressurization valve 9A then opens Refer to Figure 1B Tower 4B is now drying the main air stream while towe...

Page 6: ...Conditions The compressed air supply inlet should be checked periodically to ensure that equipment design specifications are not exceeded Normally the compressor installation includes intercoolers aft...

Page 7: ...ing Holes Desiccant Fill Port Left Tower Pressure Gauge Purge Pressure Adjustment Valve Left Tower Pressure Relief Valve Right Tower Pressure Gauge Right Tower Pressure Relief Valve Moisture Indicator...

Page 8: ...lve 3 4 19mm Dia Mounting Holes Pilot Air Filter Models 370 larger Moisture Indicator Right Tower Pressure Gauge Control Panel Electrical Entry 7 8 Purge Muffler Left Tower Pressure Gauge Purge Pressu...

Page 9: ...ifting Lugs Moisture Indicator Right Tower Pressure Gauge Control Panel Electrical Entry 7 8 Purge Mufflers Desiccant Drain Port 7 8 Dia Mounting Holes Lifting Lugs Left Tower Pressure Gauge Purge Pre...

Page 10: ...rge The dryer is shipped complete with desiccant and ready to operate after piping and electrical connections are made POWER REQUIREMENTS STANDARD CONTROL BOARD 25 THRU 60 120V 60 Hz 110V 50 Hz 34 2 0...

Page 11: ...ting Indicator Yellow Purge Economizer 50 Setting Indicator Yellow Purge Economizer 40 Setting Indicator Yellow Purge Economizer 30 Setting Indicator Yellow Alarm Reset Selection Mode Switch Purge Eco...

Page 12: ...0 switches 1 and 3 are ON switch 2 is OFF Purge Economizer Setting Standard or High Cycle Mode Selection Pressure Selection Switch No 1 2 3 4 5 6 Standard 10 minute cycle OFF ON 150 psig OFF MWP 4 min...

Page 13: ...tching failure alarm alarm light may be activated if unit is energized before it is pressurized To deactivate alarm allow dryer to cycle to next step and press the reset button 3 1 4 Adjust the purge...

Page 14: ...nimum level NOTE Adjustment must be made while a tower is purging air exhausting from muffler 3 2 2 4 Alarms 3 2 2 4 1 Switching Failure Alarm The switching failure alarm operates by sensing tower pre...

Page 15: ...uld read line pressure No air should be leaking from purge repressurization valve of the on line tower 2 Tower pressure gauge of tower off line should read below 2 psig while tower is purging If exces...

Page 16: ...4 2 kgf cm2 for dryers operated on a 10 minute cycle 80 psig 5 6 kgf cm2 for dryers operated on a 4 minute cycle 250 psig 17 6 kgf cm2 MWP models 125 psig 8 8 kgf cm2 for dryers operated on a 10 minu...

Page 17: ...071 INLET psig PRESSURE kgf cm2 MULTIPLIER TABLE 3G Maximum Purge Flow Factor DRYER MWP 150 psig 250 psig INLET PRESSURE psig 60 100 110 120 130 140 150 125 150 175 200 225 250 0 175 0 168 0 162 0 15...

Page 18: ...esiccant Do not tamp desiccant 4 1 2 5 Replace the fill plug us ing teflon tape sealant or equivalent 4 1 2 6 Repeat this procedure for the other drying tower 4 1 3 Insuring desiccant dryness 4 1 3 1...

Page 19: ...by default 4 5 2 4 After troubleshooting is completed reset the cycle selector to the desired position Use the reset switch to manually step through the dryer operating sequence until the left tower...

Page 20: ...20 160 140 120 100 80 60 40 20 0 10 20 30 40 50 60 70 80 90 100 TEMPERATURE RANGE VERSUS AVERAGE DEMAND THERMISTOR TEMPERATURE RANGE F AVERAGE DEMAND READING FIGURE4C...

Page 21: ...alve for obstruction Check power to valve pilot valve on Models 370 and larger to determine if valve or timer iis at fault Check valve for obstruction Models 370 and larger Check pilot valve and pilot...

Page 22: ...22...

Page 23: ...23...

Page 24: ...arranty shall be warranted for the unexpired portion of the warranty applying to the original product The foregoing is the exclusive remedy of any buyer of the manufacturer s product The maximum damag...

Reviews: