SPX FLOW DH-2100 Instruction Manual Download Page 15

15

150 psig MWP

100%

234 sec.

90%

211 sec.

80%

187 sec.

70%

164 sec.

60%

140 sec.

50%

117 sec.

40%

94 sec.

30%

70 sec.

250 psig MWP

100%

174 sec.

90%

157 sec.

80%

139 sec.

70%

122 sec.

60%

104 sec.

50%

87 sec.

40%

70 sec.

30%

52 sec.

            9B                 Cl       OPEN       CLOSED             CLOSED

                          6"        (

2

)

ECONOMIZER SWITCH

PURGE TIME

SETTING

                                                   TIME (Min.)

                    0      1      2      3      4      5      6      7      8       9       10
  

3A                                   OPEN                                                 CLOSED

  3B                                    CLOSED                                                OPEN

  9B                 Cl 6"              OPEN (1)          Cl                              CLOSED

  9A                                    CLOSED                         Cl             OPEN                   CLOSED
                                                                                 6"               (1)

3.2.2.5  Tower status lights -  indicate when left and right

towers are drying and regenerating.

3.2.2.6 Valve energized lights
Four LEDs are furnished on controller to indicate which air

control valves are energized at any particular time

3.2.2.7 Average Demand Meter
The demand meter displays the average demand on the

dryer for the last 4 cycles. It is determined by dividing 40 (time
to complete 4 cycles at full flow) by the actual time to complete
the last 4 cycles.

3.2.2.8  Tower pressure gauges
3.2.2.8.1 
 Periodically check tower pressure gauges to

verify that tower pressure gauge of tower on-line reads line
pressure and tower pressure gauge of tower off-line reads
below 2 psig.

NOTE

Read off-line tower gauge when tower is purging (air

exhausting from muffler)

3.2.2.8.2 Check mufflers for back pressure
Excessive back pressure may result due to the accumu-

lation of dust in the muffler.  This sometimes occurs after start-
up because of dusting of the desiccant during tower filling and
dryer transport.

If the tower pressure gauge of the off-stream tower rises

out of the black area on the gauge dial, muffler elements
should be replaced.  A set of purge exhaust muffler replace-
ment elements is supplied with the dryer.

3.2.3  All MODELS -  Determine if air control valves are

operating and sequencing correctly.

Refer to Section 1.2 and Figure 1A and 1B for a general

description of operating sequence.

3.2.3.1 Inlet switching and purge/repressurization valves.
1) Tower pressure gauge of tower on-line should read line

pressure. No air should be leaking from purge/repressurization
valve of the on-line tower.

2) Tower pressure gauge of tower off-line should read below 2

psig while tower is purging. If excessive purge air is exhausting
during purge cycle, inlet valve may have failed to close or a check
valve may be sticking.

3.2.3.2 Check valves
Check valve sticking will result in excessive air discharge

through a muffler. If excessive air is  discharged through the muffler
on the left, check if valve 5a or 5d is sticking.  If excessive air is
discharged through the muffler on the right, check  if valve 5b or 5c
is sticking.

 3.2.3.3 Operating Sequence
For dryers with standard controller and dryers with automatic

purge saving system operating on a fixed time cycle-

Figure 3C and Table 3C show valve sequence times when

dryer is operating on a 10 minute cycle.  

Figure 3D and Table 3D

show sequence times when dryer is operating on a four minute
cycle.

                                             TIME (MIN)

                           0                1                   2                 3              4

            3A                                OPEN                             CLOSED

            3B                               CLOSED                            OPEN

(1) See table 3C for open times.

VALVE

  PRESSURE

       9A                                CLOSED               CI       OPEN       CLOSED
                                                                        6"          (

2

)

(2) See table 3D for open times.

3.3 Shut  Down

3.3.1 Depressurize dryer
3.3.1.1
 Open by-pass valve (if one is installed) and close inlet

and outlet isolation valves.

3.3.1.2 Run timer through a tower change cycle until pressure

gauges on both towers read 0 psig.

3.3.2 De-energize dryer
Turn dryer off using on-off switch (indicating lights extin-

guished).

3.4 Loss of Power

Control valves are designed so that upon loss of power the  air

dryer is capable of drying air until the desiccant exposed to the air
flow is saturated.

TABLE 3D  Purge valve open times for dryers operating on a 4 minute cycle.

VALVE

FIGURE 3D  For dryers operating on a 4 minute cycle

TABLE 3C  Purge valve open times for dryers operating on a 10 minute cycle.

FIGURE 3C  For dryers operating on a 10 minute cycle

150 psig MWP

100%

66 sec.

90%

59 sec.

80%

53 sec.

70%

46 sec.

60%

40 sec.

50%

33 sec.

40%

26 sec.

30%

20 sec.

250 psig MWP

100%

42 sec.

90%

38 sec.

80%

34 sec.

70%

29 sec.

60%

25 sec.

50%

21 sec.

40%

17 sec.

30%

13 sec.

  PRESSURE

ECONOMIZER SWITCH

PURGE TIME

SETTING

Summary of Contents for DH-2100

Page 1: ...ure containing device Do not exceed maximum operating pressure as shown on equipment serial number tag Make sure equipment is depressurized before working on or disassembling it for service 2 Electric...

Page 2: ...l check points 14 3 3 Shut down 15 3 4 Loss of power 15 3 5 Design parameters 16 3 6 Determining purge and outlet flows 16 3 7 Outlet dew points vs inlet temperatures 16 4 0 MAINTENANCE 18 4 1 Desicca...

Page 3: ...WLY pressurize unit 3 Energize dryer by turning on off switch on I is on O is off 4 Adjust purge air flow rate Turn purge rate valve until Purge Pressure Gauge reads as shown in the following table NO...

Page 4: ...to as the heat of adsorption and is stored in the bed for use during regeneration Desiccant is regenerated by driving off desorbing the water collected on its surface Pressure swing also called heatl...

Page 5: ...me period air inlet switching valve 3B opens and inlet switching valve 3A closes purge and repressurization valve 9A then opens Refer to Figure 1B Tower 4B is now drying the main air stream while towe...

Page 6: ...Conditions The compressed air supply inlet should be checked periodically to ensure that equipment design specifications are not exceeded Normally the compressor installation includes intercoolers aft...

Page 7: ...ing Holes Desiccant Fill Port Left Tower Pressure Gauge Purge Pressure Adjustment Valve Left Tower Pressure Relief Valve Right Tower Pressure Gauge Right Tower Pressure Relief Valve Moisture Indicator...

Page 8: ...lve 3 4 19mm Dia Mounting Holes Pilot Air Filter Models 370 larger Moisture Indicator Right Tower Pressure Gauge Control Panel Electrical Entry 7 8 Purge Muffler Left Tower Pressure Gauge Purge Pressu...

Page 9: ...ifting Lugs Moisture Indicator Right Tower Pressure Gauge Control Panel Electrical Entry 7 8 Purge Mufflers Desiccant Drain Port 7 8 Dia Mounting Holes Lifting Lugs Left Tower Pressure Gauge Purge Pre...

Page 10: ...rge The dryer is shipped complete with desiccant and ready to operate after piping and electrical connections are made POWER REQUIREMENTS STANDARD CONTROL BOARD 25 THRU 60 120V 60 Hz 110V 50 Hz 34 2 0...

Page 11: ...ting Indicator Yellow Purge Economizer 50 Setting Indicator Yellow Purge Economizer 40 Setting Indicator Yellow Purge Economizer 30 Setting Indicator Yellow Alarm Reset Selection Mode Switch Purge Eco...

Page 12: ...0 switches 1 and 3 are ON switch 2 is OFF Purge Economizer Setting Standard or High Cycle Mode Selection Pressure Selection Switch No 1 2 3 4 5 6 Standard 10 minute cycle OFF ON 150 psig OFF MWP 4 min...

Page 13: ...tching failure alarm alarm light may be activated if unit is energized before it is pressurized To deactivate alarm allow dryer to cycle to next step and press the reset button 3 1 4 Adjust the purge...

Page 14: ...nimum level NOTE Adjustment must be made while a tower is purging air exhausting from muffler 3 2 2 4 Alarms 3 2 2 4 1 Switching Failure Alarm The switching failure alarm operates by sensing tower pre...

Page 15: ...uld read line pressure No air should be leaking from purge repressurization valve of the on line tower 2 Tower pressure gauge of tower off line should read below 2 psig while tower is purging If exces...

Page 16: ...4 2 kgf cm2 for dryers operated on a 10 minute cycle 80 psig 5 6 kgf cm2 for dryers operated on a 4 minute cycle 250 psig 17 6 kgf cm2 MWP models 125 psig 8 8 kgf cm2 for dryers operated on a 10 minu...

Page 17: ...071 INLET psig PRESSURE kgf cm2 MULTIPLIER TABLE 3G Maximum Purge Flow Factor DRYER MWP 150 psig 250 psig INLET PRESSURE psig 60 100 110 120 130 140 150 125 150 175 200 225 250 0 175 0 168 0 162 0 15...

Page 18: ...esiccant Do not tamp desiccant 4 1 2 5 Replace the fill plug us ing teflon tape sealant or equivalent 4 1 2 6 Repeat this procedure for the other drying tower 4 1 3 Insuring desiccant dryness 4 1 3 1...

Page 19: ...by default 4 5 2 4 After troubleshooting is completed reset the cycle selector to the desired position Use the reset switch to manually step through the dryer operating sequence until the left tower...

Page 20: ...20 160 140 120 100 80 60 40 20 0 10 20 30 40 50 60 70 80 90 100 TEMPERATURE RANGE VERSUS AVERAGE DEMAND THERMISTOR TEMPERATURE RANGE F AVERAGE DEMAND READING FIGURE4C...

Page 21: ...alve for obstruction Check power to valve pilot valve on Models 370 and larger to determine if valve or timer iis at fault Check valve for obstruction Models 370 and larger Check pilot valve and pilot...

Page 22: ...22...

Page 23: ...23...

Page 24: ...arranty shall be warranted for the unexpired portion of the warranty applying to the original product The foregoing is the exclusive remedy of any buyer of the manufacturer s product The maximum damag...

Reviews: