![Spring Air Systems AP10C Maintenance Manual Download Page 10](http://html1.mh-extra.com/html/spring-air-systems/ap10c/ap10c_maintenance-manual_1351514010.webp)
_____________________________________________________________________________________________
Spring Air Systems Water Wash Ventilator Maintenance Manual 11/01
8
WASH TIMER SETTINGS
All SB10C, MP10C, MP20C, MP30C, MP40C, & MP50C wash control panel timers are factory set at two minutes.
All SB10H, MP10H, MP20H, MP30H, MP40H, & MP50H wash control panel timers are factory set at three minutes.
After the first four days of operation open the front access door on the grease extractor. Visually check if the baffle and
interior surfaces are clean. If there are grease deposits check that the hot water pressure is between 40 psi (2.8 kg/cm2)
and 70 psi (4.2 kg/cm2) and the hot water temperature is between 120 F (49 C) and 180 F (82 C). If there is adequate
temperature and pressure either use a higher detergent concentration or increase the wash time.
•
The detergent concentration can be adjusted by increasing the cam setting on the side of the detergent pump.
Loosen the wing nut on the side of the detergent pump and rotate the cam to the next setting. The cam is
adjustable from 0 to 6, 6 being the highest detergent concentration. Only increase one setting at a time. Inspect
the interior each day and adjust until all surfaces are clean.
•
Only increase the wash time in 30-second intervals until all baffles and exposed interior grease extractor surfaces
are clean.
For type “C” water wash ventilators check that the cold water pressure is at least 10 psi 1.4 kg/cm2).
AUTOMATIC WASH SYSTEMS:
SBA10H, SBA10C, AP10H, AP10C, AP20H, AP20C, AP30H, AP30C, AP40H,
AP40C, AP50H, & AP50C
The automatic wash control panels are equipped with a solid-state microprocessor. The fan
selector switch is replaced with a three-position “OFF/AUTO/ON” switch. In the “OFF” and “ON”
positions the control panel operates identical to the standard SB, & MP manual wash panels.
When the fan switch is rotated to the “AUTO” position the solid-state time clock controls the
OFF/ON operation of the exhaust fan, supply fan and wash cycle.
Setting the clock (T6) is as simple as setting a digital watch.
Automatic Wash Panel
Figure 12a
SBA10C and SBA10H Automatic Wash Panel Wiring Schematic
Figure 12b
NOTE 1:
ALL REMOTE ELECTRIAL WIRING
AND NATIONAL CODE REQUIREMENTS
SHALL CONFORM TO ALL LOCAL
INTERNAL WIRING BY SPRING AIR
Q: 1 2 3 4 RUN
Mo 09:00
I: 1 2 3 4 5 6
SMART RELAY
Q1
L
Q2
N
I1
I2
FAN SWITCH
OFF/AUTO/ON
PUMP
DETERGENT
HOT WATER SOLENOID
WASH PILOT
H
B
FAN PILOT
OPTIONAL COLD
WATER SOLENOID
C
G
ESC
Q3
OK
Q4
I3
I4
I5
I6
CURCUIT BREAKER
4
4
8
9
3
5
1
END SWITCH
TWO (2) WIRES TO THE
MOTOR STARTERS OVERLOADS
5
1
RED
WHITE
WET CHEMICAL CONTROL
HEAD 120V/1/60 - 1A.
ELECTRICAL DIVISION
AND DISCONNECTS BY
NOTE 2:
SHUTOFF DAMPER AND END SWITCH 120V/1/60
(OPTIONAL) THREE (3) WIRES TO SUPPLY AIR MOTORIZED
MOTOR STARTER - 120V/1/60 - 2 AMPS MAXIMUM
(OPTIONAL) POWER SUPPLY TO SUPPLY FAN
LV10 PANEL - 120V/1/60 - 2 AMPS MAXIMUM.
POWER TO THE SPRING AIR SYSTEMS ENVIRO FILTER UNIT
POWER TO THE EXHAUST FAN MOTOR STARTER
24 HOURS/DAY - 120V/1/60 - 15 AMPS
POWER SUPPLY TO THE SB10H/C PANEL
NORMALLY OPEN
2 AMPS MAXIMUM.
9
4
8
9
4
REMOTE WIRING BY TRADES
120V/1/60 - 2 AMPS MAXIMUM.
3
4
4
1
OR
x x o
x
o
x
o
o
x