Spirax Sarco TD120 Installation And Maintenance Instructions Manual Download Page 8

IM-P150-07 

 ST Issue 4

8

5. Operation

The  TD120  is  a  thermodynamic  steam  trap  which  uses  a  disc  to  control  the  release  of 
condensate and to trap steam. The trap cycles open and closed to discharge condensate, 
close to steam temperature, and closes tight between discharges. 
The disc, which is the only moving part, rises and falls in response to dynamic forces produced 
by the partial re-evaporation (flashing) of hot condensate. Cool condensate, air and other                    
non-condensible gases enters the trap through the central orifice, lifts the disc, and discharges 
through the outlet orifice.  When the condensate approaches steam temperature, a portion of it 
flashes as it enters the trap. The flash steam passes at high velocity over the underside of the 
disc and collects in the control chamber above. The resulting pressure imbalance, forces the 
disc downward onto the seating surfaces, stopping the flow. The trap remains tightly closed 
until the loss of heat through the trap body lowers the control chamber pressure, allowing the 
inlet pressure to raise the disc and repeat the cycle.

4.1  Commissioning with particular reference to venting air

Initial  start-up  can  take  several  hours  (or  days)  to  bring  the  system  to  normal  operating 
pressure and temperature. Even if the trap has replaced another trap while the main system 
has remained running, it may still be necessary to vent air from the drop leg. If the trap is 
some distance from stop valve '

A

' (Figure 2), it could be possible to air lock the pipework 

between valve '

A

' and the trap (i.e. the trap closes to air and does not readily allow steam to 

enter the pipework). To overcome this on start-up the following procedure should be adopted. 
With the stop valve '

B

' closed, drain valve '

C

' open, slowly and partially open stop valve '

A

'. 

This will discharge the air, condensate and any pipe debris.
Valve '

C

' should then be fully closed, and valves '

A

' and '

B

' slowly opened to the fully open 

position. When the trap is more than 2 m (6 ft) away from the vertical drain leg, a suitable drop 
leg at the inlet to the trap can improve its service life by ensuring that the trap does not see a 
mixture of steam and condensate.

Important note

After the trap has been in service at normal operating pressure and temperature for                  
24 hours, it is essential that the cover nuts be retightened (see Table 1, page 11). This will 
ensure the correct compression of the gasket under service conditions. 

4. Commissioning

Summary of Contents for TD120

Page 1: ...ic Steam Trap Installation and Maintenance Instructions IM P150 07 ST Issue 4 1500050 4 1 Safety information 2 General product information 3 Installation 4 Commissioning 5 Operation 6 Maintenance 7 Spare parts Printed in the UK Copyright 2007 ...

Page 2: ...fically designed for use on steam air or condensate water which is in Group 2 of the above mentioned Pressure Equipment Directive The products use on other fluids may be possible but if this is contemplated Spirax Sarco should be contacted to confirm the suitability of the product for the application being considered ii Check material suitability pressure and temperature and their maximum and minimu...

Page 3: ...hocks 1 7 Pressure systems Ensure that any pressure is isolated and safely vented to atmospheric pressure Consider double isolation double block and bleed and the locking or labelling of closed valves Do not assume that the system has depressurised even when the pressure gauge indicates zero 1 8 Temperature Allow time for temperature to normalise after isolation to avoid danger of burns 1 9 Tools ...

Page 4: ...e product from an installation refer to Maintenance instructions 1 14 Freezing Provision must be made to protect products which are not self draining against frost damage in environments where they may be exposed to temperatures below freezing point 1 15 Disposal Unless otherwise stated in the Installation and Maintenance Instructions this product is recyclable and no ecological hazard is anticipa...

Page 5: ... 23 EC Certification This product is available with certification to EN 10204 3 2 Note All certification inspection requirements must be stated at the time of order placement Note For additional information see Technical Information Sheet TI P150 01 2 2 Sizes and pipe connections and 1 Butt weld ends to suit Schedule 160 pipe and 1 Socket weld ends to ANSI B 16 11 Class 6000 DN15 and DN25 standard...

Page 6: ...bar g 522 C 3626 psi g 972 F TMA Maximum allowable temperature 550 C 153 bar g 1022 F 2220 psi g Minimum allowable temperature 29 C 20 F PMO Maximum operating pressure 250 bar g 3626 psi g for saturated steam service TMO Maximum operating temperature 550 C 153 bar g 1022 F 2220 psi g Minimum operating temperature 0 C 32 F Note For lower operating temperatures consult Spirax Sarco PMOB Maximum oper...

Page 7: ... leg preceding the trap Access for removal of the integral strainer screen should also be provided 3 5 Suitable isolation valves must be installed to allow for safe maintenance and trap replacement Where the trap discharges into a closed return system a non return valve should be fitted downstream to prevent flow 3 6 Always open isolation valves slowly until normal operating conditions are achieved ...

Page 8: ...ference to venting air Initial start up can take several hours or days to bring the system to normal operating pressure and temperature Even if the trap has replaced another trap while the main system has remained running it may still be necessary to vent air from the drop leg If the trap is some distance from stop valve A Figure 2 it could be possible to air lock the pipework between valve A and ...

Page 9: ...Stop valve A Stop valve B TD120 Strainer Optional Dirt pocket dirt leg To drain or return To drain or return Fig 2 Typical installation Alternative layout Suggested drop leg if the TD120 is located more than 2 m 6 away from the main drop leg To drain ...

Page 10: ...ng torques see Table 1 After 24 hours in service and when reassembling the nuts should be tightened in a diagonally opposite sequence Open the isolation valves slowly until normal operating conditions are achieved Check for leaks 6 2 How to clean or replace the strainer Access to the strainer screen can be obtained by undoing the nuts 8 and removing the bottom cover Remove the strainer screen 4 Fi...

Page 11: ...IM P150 07 ST Issue 4 11 Table 1 Recommended tightening torques or Item Part N m lbf ft mm 4 22 A F 25 35 18 26 8 Nut 23 A F M16 160 180 118 132 8 Stud M16 85 90 62 5 66 8 2 6 7 7 4 8 Fig 3 ...

Page 12: ... Set of internals 2 7 2 off 4 Strainer screen 4 7 Set of cover gaskets 7 2 off Set of cover studs and nuts 8 8 off 9 How to order spares Always order spares by using the description given in the column headed Available spares and state the size and type of trap Example 1 Strainer screen for a Spirax Sarco DN15 TD120 thermodynamic steam trap Fig 3 8 8 4 7 2 7 8 8 ...

Reviews: