IM-P706-03
CTLS Issue 1
48
SP7-20 Smart Positioner
Error code
Possible cause
Impact
Troubleshooting
ERROR 21
Error while processing the
measured values, pointing to an
error in the working data (RAM).
The actuator is moved to the
safe position. After approx.
5 seconds, the positioner is
automatically reset and the
RAM is reinitialized.
If the error persists even after
the positioner has been reset,
the device will need to be
returned to the manufacturer
for repair.
ERROR 22
E r r o r d u r i n g t h e t a b l e
processing, pointing to an
error in the working data (RAM).
The actuator is moved to the
safe position. After approx.
5 seconds, the positioner is
automatically reset and the
RAM is reinitialized.
If the error persists even after
the positioner has been reset,
the device will need to be
returned to the manufacturer
for repair.
ERROR 23
Error when verifying the
checksum of the configuration
data (RAM).
The actuator is moved to the
safe position. After approx.
5 seconds, the positioner is
automatically reset and the
RAM is reinitialized.
If the error persists even after
the positioner has been reset,
the device will need to be
returned to the manufacturer
for repair.
ERROR 24
Error in the processor function
registers (RAM).
The actuator is moved to the
safe position. After approx.
5 seconds, the positioner is
automatically reset and the
RAM is reinitialized.
If the error persists even after
the positioner has been reset,
the device will need to be
returned to the manufacturer
for repair.
ERROR 50 to 99
Internal error.
The actuator is moved to the
safe position. After approx.
5 seconds, the positioner is
automatically reset.
If the error can be reproduced
and occurs in the same
position after resetting, the
device must be returned for
repair to the manufacturer.
6.1 SP7-20 Error codes
(continued)
Summary of Contents for SP7-20
Page 9: ...IM P706 03 CTLS Issue 1 9 SP7 20 Smart Positioner...
Page 39: ...IM P706 03 CTLS Issue 1 39 SP7 20 Smart Positioner Fig 21 5 2 SP7 20 HART Parameter Overview...
Page 55: ...IM P706 03 CTLS Issue 1 55 SP7 20 Smart Positioner...