IM-P706-03
CTLS Issue 1
40
SP7-20 Smart Positioner
5.2.1 SP7-20 Parameter description HART
Parameter
Display
Function
Possible
parameter
setting
Unit
Factory
setting
P1._
STANDARD
P1.0
ACTUATOR
Actuator type
Actuator type
LINEAR, ROTARY
---
LINEAR
P1.1
AUTO_ADJ
Automatic
adjustment
Autoadjust
Function
---
---
P1.2
ADJ_MODE
Auto adjust
mode
Automatic
adjustment
mode
FULL,
STROKE,CTRL_PAR,
ZERO_POS,
LOCKED
FULL
P1.3
TEST
Test
Test
Function
---
INACTIVE
P1.4
FIND_DEV
Find device
Find device
DISABLE, ONE TIME,
CONTINOUS
---
DISABLE
P1.5
EXIT
Return
Return to
operating level
Function
---
NV_SAVE
P2._
SETPOINT
P2.0
MIN_RGE
Min setpoint
range
Min. setpoint
range
4.0 to 18.4
mA
4.0
P2.1
MAX_RGE
Max setpoint
range
Max. setpoint
range
20.0 to 5.6
mA
20.0
P2.2
CHARACT
Charact.
curve
Characteristic
curve
LINEAR, 1:25, 1:50,
25:1, 50:1, USERD
---
LINEAR
P2.3
ACTION
Valve action
Direction of
action
DIRECT, REVERSE
---
DIRECT
P2.4
SHUT_CLS
Shut-off value
0%
Shut-off value
0 %
OFF, 0.1 to 45.0
%
1.0
P2.5
SHUT_OPN
Shut off value
100%
Shut-off value
100%
55.0 to 100.0, OFF
%
OFF
P2.6
RAMP UP
Set point
ramp, up
Setpoint ramp
(up)
OFF, 0 to 200
---
OFF
P2.7
RAMP DN
Set point
ramp, down
Setpoint ramp
(down)
OFF, 0 to 200
---
OFF
P2.8
EXIT
Return
Return to
operating level
Function
---
NV_SAVE
P3._
ACTUATOR
P3.0
MIN_RGE
Min. of stroke
range
Operating
range, min.
0.0 to 90.0
%
0.0
P3.1
MAX_RGE
Max. of stroke
range
Operating
range, max.
100.0 to 10.0
%
100
P3.2
ZERO_POS
Zero position
Zero position
CLOCKWISE,
CTCLOCKWISE
---
CTCLOCKWISE
P3.3
EXIT
Return
Return to
operating level
Function
---
NV_SAVE