IM-P706-03
CTLS Issue 1
30
SP7-20 Smart Positioner
3.3.4 Pneumatic connections - Air supply
Instrument air*
Purity
Maximum particle size: 5 μm
Maximum particle density: 5 mg/m
3
Oil content
Maximum concentration 1 mg/m
3
Pressure dew point
10 K below operating temperature
Supply pressure**
Standard design:
1.4 to 6 bar (20 to 90 psi)
Air consumption***
< 0.03 kg/h/0.015 scfm
*
Free of oil, water and dust in accordance with DIN/ISO 8573-1. Pollution and oil content in accordance
with Class 3:3:3
**
Do not exceed the maximum output pressure of the actuator
***
Independent of supply pressure
Summary of Contents for SP7-20
Page 9: ...IM P706 03 CTLS Issue 1 9 SP7 20 Smart Positioner...
Page 39: ...IM P706 03 CTLS Issue 1 39 SP7 20 Smart Positioner Fig 21 5 2 SP7 20 HART Parameter Overview...
Page 55: ...IM P706 03 CTLS Issue 1 55 SP7 20 Smart Positioner...
Page 56: ...IM P706 03 CTLS Issue 1 56 SP7 20 Smart Positioner...