background image

IM-P704-03

 CTLS Issue 3

1

PP6 Positioner

© Copyright 2021 

Printed in GB

PP6 Positioner 

Quick Start Guide

IM-P704-03

 

CTLS Issue 3

This guide covers only a brief description of installation and maintenance for 

Spiratrol and QL valves. For detailed installation, operations, maintenance 

including safety, precautions, and warnings, please refer to our official instruction 

manual at www.spiraxsarco.com (IM-P704-02).

PP6 is Pneumatic-Pneumatic Positioner that accurately controls valve stroke in response to a pneumatic 

input signal of 0.02~0.1 MPa (0.2~1 bar) from the controller.

! NOTE: Use of the positioner in a hazardous area. 

1  The positioner must be suitably earthed to prevent static electricity

2  Operation with air hotter than 70 °C is to be avoided

3

The positioner must not be used in a Zone 0 area.

4

Only wipe the positioner with a damp cloth to prevent static build up.

Summary of Contents for PP6

Page 1: ...er to our official instruction manual at www spiraxsarco com IM P704 02 PP6 is Pneumatic Pneumatic Positioner that accurately controls valve stroke in response to a pneumatic input signal of 0 02 0 1...

Page 2: ...hand side of the actuator yoke 1 1 3 Make sure that Positioner s feedback lever is perpendicular to the valve stem at 50 of the valve stroke 1 1 4 The feedback pin coming from the actuator coupling sh...

Page 3: ...ctuator s stem height And then assemble the positioner with the brackets by using M6 bolts washers and nuts 1 2 3 Make sure that the center of positioner s main shaft is well aligned with the center o...

Page 4: ...ng input signal Supply Span Signal Signal 2 1 2 Piping and span direction setting for linear RA single actuator 2 1 3 Piping and cam direction setting for rotary single actuator Move downward at pneum...

Page 5: ...action Note For central mount reverse the Span lever Supply Span When increasing input signal Reverse action Note For central mount reverse the Span lever Signal Supply Signal 2 2 2 Piping and cam di...

Page 6: ...Above two steps are required several times until both zero and span are properly set 3 2 4 After proper setting tighten lock screw of the span unit 3 3 Adjustment A M switch Auto Manual 3 3 1 Auto ma...

Page 7: ...34 EU C 03 issue 2 EN Product Integrity Compliance Manager place and date of issue This declaration of conformity is issued under the sole responsibility of the manufacturer The object of the declarat...

Page 8: ...079 37 2016 0 0 0 0 As amended by EU Exit Regulations References to the relevant designated standards used or references to the other technical specifications in relation to which conformity is declar...