background image

IM-P704-03

 CTLS Issue 3

2

PP6 Positioner

1. Installation

Side view 

shown for 

clarity

1.1 Linear positioner

1.1.1 

Assemble feedback pin locator and feedback 

pin to actuator coupling firmly.

Mounting 

Positions

Pin 

Locator 

Marking

Valve 

stroke

MTG

 kit

Feedback 

pin 

locator 

direction

Central

N/A

20

PY1

30

50

PY2

70

Left hand 

side

D

20

UY3

A

30

B

50

UY1

E

70

1.1.2 

Assemble the supplied feedback lever and 

bracket to positioner firmly, then loosely 

mount the assembly on the left hand side of 

the actuator yoke. For central mount, mount 

on the right hand side of the actuator yoke.

1.1.3 

Make sure that Positioner’s feedback lever is 

perpendicular to the valve stem at 50% of the 

valve stroke.

1.1.4 

The feedback pin coming from the actuator 

coupling should be inserted inside slot of the 

feedback lever in such a way that the length 

of va l ve st r o ke c o i n c i d e s w i t h t h e 

corresponding figures in “mm” marked on the 

feedback lever.

Improper setting may cause poor linearity or 

damage to positioner.

1.1.5 

At 0% or 100% position, the linear lever or 

linear lever stopper should not touch the 

stopping bosses of positioner.

1.1.6 

As a final step, tighten the bracket to the 

actuator yoke.

50%

90°

Lever spring

Feedback pin

Stopping bosses

Linear lever stopper

Stopping bosses

Linear lever stopper

No

 to

uch

Summary of Contents for PP6

Page 1: ...er to our official instruction manual at www spiraxsarco com IM P704 02 PP6 is Pneumatic Pneumatic Positioner that accurately controls valve stroke in response to a pneumatic input signal of 0 02 0 1...

Page 2: ...hand side of the actuator yoke 1 1 3 Make sure that Positioner s feedback lever is perpendicular to the valve stem at 50 of the valve stroke 1 1 4 The feedback pin coming from the actuator coupling sh...

Page 3: ...ctuator s stem height And then assemble the positioner with the brackets by using M6 bolts washers and nuts 1 2 3 Make sure that the center of positioner s main shaft is well aligned with the center o...

Page 4: ...ng input signal Supply Span Signal Signal 2 1 2 Piping and span direction setting for linear RA single actuator 2 1 3 Piping and cam direction setting for rotary single actuator Move downward at pneum...

Page 5: ...action Note For central mount reverse the Span lever Supply Span When increasing input signal Reverse action Note For central mount reverse the Span lever Signal Supply Signal 2 2 2 Piping and cam di...

Page 6: ...Above two steps are required several times until both zero and span are properly set 3 2 4 After proper setting tighten lock screw of the span unit 3 3 Adjustment A M switch Auto Manual 3 3 1 Auto ma...

Page 7: ...34 EU C 03 issue 2 EN Product Integrity Compliance Manager place and date of issue This declaration of conformity is issued under the sole responsibility of the manufacturer The object of the declarat...

Page 8: ...079 37 2016 0 0 0 0 As amended by EU Exit Regulations References to the relevant designated standards used or references to the other technical specifications in relation to which conformity is declar...

Reviews: