IM-P402-129
EMM Issue 7
30
10.5 Cable / wire and connector data
Mains and signal connector
Termination
Rising clamp plug-in terminal blocks with screw connectors
Cable size
0.2 mm
²
(24 AWG) to 2.5 mm
²
(12 AWG).
Stripping length
5 - 6 mm
Caution:
Use only the connectors supplied by Spirax Sarco Ltd. Safety and Approvals may
be compromised otherwise.
Level probe cable / wire
Type
High temperature
Shield type
Screened
Number of cores
5
Gauge
1 – 1.5 mm
²
(18 - 16 AWG)
Maximum length
100 m (328 ft)
10.6 Input technical data
Level probe (conductivity)
Switching conductivity
1 µS / cm @ 25 °C, K = 0.22 (220 KΩ)
Drive
ac – pulsed
Summary of Contents for LC1350