![Spirax Sarco CA44 Installation And Maintenance Instructions Manual Download Page 7](http://html1.mh-extra.com/html/spirax-sarco/ca44/ca44_installation-and-maintenance-instructions-manual_1348011007.webp)
IM-P148-37
ST Issue 3
7
The product
must not
be used in this region.
A
-
B
Flanged EN 1092 PN40, ASME 300, screwed and socket weld
A
-
C
Flanged JIS/KS 20K
A
-
D
Flanged ASME 150
∆
PMX - Maximum differential pressure
Depending on the specific gravity of the liquid being drained.
Specific gravity
Trap
1.0 0.9 0.8 0.7 0.6
Maximum differential pressure bar (psi)
CA44-32
32.0 (464.00) 32.0 (464.00) 29.0 (420.50) 20.0 (290.00) 12.0 (174.00)
CA44S-4.5
4.5 (65.25)
4.5 (65.25)
4.5 (65.25)
3.4 (49.30) 2.0 (29.00)
CA44S-10
10.0 (145.00)
9.5 (137.75)
6.8 (98.60)
5.5 (79.75) 3.4 (49.30)
CA44S-14
14.0 (203.00) 14.0 (203.00) 11.0 (159.50)
8.0 (116.00) 5.0 (72.50)
CA44S-21
21.0 (304.50) 19.0 (275.50) 15.0 (217.50) 10.0 (145.00) 6.5 (94.25)
CA44S-32
32.0 (464.00) 30.0 (435.00) 23.0 (333.50) 16.5 (239.25) 10.0 (145.00)
Pressure bar g
Temperature
°
C
A
B
D
C
Pressure bar g
Temperature
°
C
A
B
D
C
Operating range
CA44
CA44S
Summary of Contents for CA44
Page 16: ...IM P148 37 ST Issue 3 16...