background image

IM-P017-03  ST Issue 5

5

3. Installation

Note: Before actioning any installation observe the 'Safety information' in Section 1.

Referring to the Installation and Maintenance Instructions, name-plate and Technical Information
Sheet, check that the product is suitable for the intended installation:

3.1

Check materials, pressure and temperature and their maximum values. If the maximum
operating limit of the product is lower than that of the system in which it is being fitted,
ensure that a safety device is included in the system to prevent overpressurisation.

3.2

Determine the correct installation situation and the direction of fluid flow.

3.3

Remove protective covers from all connections.

3.4

The automatic air eliminator / air vent should be installed vertically with the inlet at the bottom.
We recommended that a drip pipe be fitted discharging to a safe place. To enable this to
be done the outlet is provided with a ¼" BSP or NPT male thread. See Fig. 2 for a typical
application.

Discharge to
safe visual point

Air bottle

Fig. 2  Typical application

The automatic air eliminator / air vent should be installed
vertically with the inlet at the bottom. We recommend piping
the discharge from the air eliminator / air vent to a suitable
safe point.

Summary of Contents for AE36

Page 1: ...ir Vents for Liquid Systems Installation and Maintenance Instructions IM P017 03 ST Issue 5 0170550 5 1 General safety information 2 General product information 3 Installation 4 Commissioning 5 Operat...

Page 2: ...maintain the product this is easily achieved by fitting Spirax Sarco depressurisation valves type DV see separate literature for details Do not assume that the system is depressurised even when a pres...

Page 3: ...water installations The body and cap are of austenitic stainless steel type 316L They are available as follows AE36 Standard air vent AE36A Standard air vent with check valve Note For further informat...

Page 4: ...owable pressure 10 bar g 150 C 145 psi g 302 F TMA Maximum allowable temperature 150 C 302 F Minimum allowable temperature 10 C 14 F PMO Maximum operating pressure 10 bar g 110 C 145 psi g 230 F TMO M...

Page 5: ...in the system to prevent overpressurisation 3 2 Determine the correct installation situation and the direction of fluid flow 3 3 Remove protective covers from all connections 3 4 Theautomaticairelimin...

Page 6: ...lever and the whole assembly screwed back into the body see Table 1 for recommended tightening torques The set of internals are supplied with a check valve ball and circlip The check valve is only re...

Page 7: ...IM P017 03 ST Issue 5 7 Table 1 Recommended tightening torques or Item N m lbf ft mm 1 30 10 12 7 0 8 6 8 Cheesehead M4 x 6 2 5 2 8 1 8 2 0 Fig 4 1 8 4 5 AE36A only...

Page 8: ...earlier versions of the AE36 designated AE36CV which operate over the range 3 to 8 bar then the spares set for the AE36A cannot be used The earlier spares set should be used How to order spares Alway...