12 Installation Manual
Vortceptor
TABLE 1
External Anti Floatation Ribs:
The wetwell bottom is designed to BS4994 to any
resist buckling of the wetwell bottom from external
water pressure and internal pressure, in the installed
condition with a compacted base to (Figure 1, below)
and the perimeter of the wetwell including the anti-
floatation Ribs embedded in concrete.
This table must be followed for the concrete slab
design for all wetwalls with fibreglass external ribs.
COLUMN 1
COLUMN 2
COLUMN 3
COLUMN 4
COLUMN 5
Wetwell
Dia.
mm
Reinforcement REO BAR
(In Center of
Slab, Ref-Figure 1.)
Required Slab
Extension
Around
Wetwell (mm)
Slab Thickness
(mm)
Required Ballast
Extension
Around
Wetwell (mm)
Ballast Height
(mm)
1200
1 @ 1800mm Dia. N12
400
200
300
400
1520
1 @ 1920mm Dia. N12
500
200
350
500
1850
1 @ 2250mm Dia. N12 &
1 @ 2650mm Dia. N12
550
200
400
600
2200
1 @ 2600mm Dia. N12 &
1 @ 3000mm Dia. FN12
700
200
500
700
2470
1 @ 2900mm Dia. N16 &
1 @ 3300mm Dia. N16
800
250
500
800
3000
1 @ 3400mm Dia. N16 &
1 @ 3800mm Dia. N16
900
300
700
1000
3500
1 @ 3900mm Dia. N20 &
1 @ 4800mm Dia. N20
1000
300
700
1200
4000
1 @ 4400mm Dia. N20 &
1 @ 4900mm Dia. N20
1100
350
750
1400
•
These slabs are designed to AS3600.
•
In some cases the slab and/or reinforcing design
is controlled by temperature requirements and in
other cases by flexure.
•
Use minimum 20Mpa concrete.
•
Since some of the slab designs are controlled
by temperature, the slab thickness should not
be increased without the approval of a Design
Engineer.
FIGURE 1