12               Installation Manual 

Vortceptor

TABLE 1

External Anti Floatation Ribs:

The wetwell bottom is designed to BS4994 to any 
resist buckling of the wetwell bottom from external 
water pressure and internal pressure, in the installed 
condition with a compacted base to (Figure 1, below) 
and the perimeter of the wetwell including the anti-
floatation Ribs embedded in concrete.

This table must be followed for the concrete slab 
design for all wetwalls with fibreglass external ribs.

COLUMN 1

COLUMN 2

COLUMN 3

COLUMN 4

COLUMN 5

Wetwell 
Dia.  
mm

Reinforcement REO BAR  
(In Center of
Slab, Ref-Figure 1.)

Required Slab 
Extension 
Around
Wetwell (mm)

Slab Thickness 
(mm)

Required Ballast 
Extension 
Around
Wetwell (mm)

Ballast Height 
(mm)

1200

1 @ 1800mm Dia. N12

400

200

300

400

1520

1 @ 1920mm Dia. N12

500

200

350

500

1850

1 @ 2250mm Dia. N12 &
1 @ 2650mm Dia. N12

550

200

400

600

2200

1 @ 2600mm Dia. N12 &
1 @ 3000mm Dia. FN12

700

200

500

700

2470

1 @ 2900mm Dia. N16 &
1 @ 3300mm Dia. N16

800

250

500

800

3000

1 @ 3400mm Dia. N16 &
1 @ 3800mm Dia. N16

900

300

700

1000

3500

1 @ 3900mm Dia. N20 &
1 @ 4800mm Dia. N20

1000

300

700

1200

4000

1 @ 4400mm Dia. N20 &
1 @ 4900mm Dia. N20

1100

350

750

1400

• 

These slabs are designed to AS3600.

• 

In some cases the slab and/or reinforcing design 
is controlled by temperature requirements and in 
other cases by flexure.

• 

Use minimum 20Mpa concrete.

• 

Since some of the slab designs are controlled 
by temperature, the slab thickness should not 
be increased without the approval of a Design 
Engineer.

FIGURE 1

Summary of Contents for Vortceptor

Page 1: ...SPEL Vortceptor spel com au Installation Manual ...

Page 2: ...y of all the individuals involved in the installation To prevent wetwell damage and or failure which could lead to product loss and environmental contamination To validate the wetwell warranty GENERAL INFORMATION WARNING Wetwells are a confined space per OHS guidelines Follow proper confined space safety procedures SPEL fibreglass wetwells are designed for installation with concrete top pad and bo...

Page 3: ...tank YES NO Install a 150mm thick compacted base This can be either a concrete blinding or compacted crushed rock layer YES NO Lower the Vortceptor into the excavation ensure no rocks or sharp objects fall into the hole and damage the tank YES NO Level and adjust the Vortceptor to suit the main drain pipework and the Diversion Chamber inlet void The invert levels of the inlet and outlet pipework i...

Page 4: ...DS bit to drill the bolt holes YES NO Use M8 x 100mm Galvanised screw bolts to fix the Vortceptor to the Diversion Chamber YES NO Associated Drainage Finishing Works Install upstream and downstream drainage pipework YES NO Connect the pipework by others to the Diversion Chamber concrete bandage the inlet and outlet pipes to the Diversion Chamber YES NO Internally render the inlet and outlet pipewo...

Page 5: ...ntal contamination A HANDLING PREPARATION WARNING Do not stand on or under wetwell while it is being lifted This could result in personal injury or death Do not drop or impact the wetwell Wetwells should be stored horizontally and chocked using only appropriate materials such as sandbags tires or other soft or pliable materials Upon wetwell delivery and when lifting wetwell visually inspect entire...

Page 6: ...are significant and are based on the method of construction not the measured densities Dumped means that there is absolutely no compaction of the embedment soil Slight means there was something done that increased the soil density even if minor such as water settling jet ting flooding equipment travel and in some cases foot traffic For stable soils cohesion 36 kpa and or a bearing capacity 170 kpa...

Page 7: ...as an underground fibreglass tank the backfill around the wetwell must also meet the tank backfill requirements so as to not compromise the tank installation Tank backfill requirements are more restricted and strict conformance to the tank backfill requirments in MAN 600 must be met for both the wetwell and tank F PIPING PENETRATIONS FITTINGS CAUTION Always wear safety glasses and protective cloth...

Page 8: ...ned to be self supporting after cured The pad shall be specified by the Certified Engineer FIBREGLASS FLAT TOPS WITHOUT TRAFFIC LOAD See Figure H 1 The pad must be larger than the wetwell a minimum of 300mm in all directions Maximum 200mm concrete pad thickness FIBREGLASS FLAT TOPS WITH TRAFFIC LOAD See Figure H 2 The pad must be larger than the wetwell a minimum of 600mm in all directions The Cer...

Page 9: ...spel com au 9 ...

Page 10: ...10 Installation Manual Vortceptor ...

Page 11: ...in minimum water level Add a minimum of 300mm of well placed backfill material MUST be crushed gravel to the hole and level the bed to assure uniform bottom support for the tank Position the tank in the hole Partially ballast tank using water until it settles firmly on the prepared bed Ballast level in a tank must never exceed water level in hole during installation Use only enough ballast to sink...

Page 12: ...ab Thickness mm Required Ballast Extension Around Wetwell mm Ballast Height mm 1200 1 1800mm Dia N12 400 200 300 400 1520 1 1920mm Dia N12 500 200 350 500 1850 1 2250mm Dia N12 1 2650mm Dia N12 550 200 400 600 2200 1 2600mm Dia N12 1 3000mm Dia FN12 700 200 500 700 2470 1 2900mm Dia N16 1 3300mm Dia N16 800 250 500 800 3000 1 3400mm Dia N16 1 3800mm Dia N16 900 300 700 1000 3500 1 3900mm Dia N20 1...

Page 13: ...spel com au 13 ...

Page 14: ...A OFFICE 9 Hampden Road Mount Barker SA 5251 P 1300 773 500 E sales spel com au WA OFFICE 2 Modal Crescent Canning Vale WA 6155 P 61 8 9350 1000 P 1800 335 550 E sales spel com au NZ OFFICE AUCKLAND 100 Montgomerie Road Airport Oaks P 64 9 276 9045 E sales spel com au NZ OFFICE WANGANUI 43 Heads Road Wanganu New Zealand P 64 6 349 0088 E sales spel com au NZ OFFICE WELLINGTON 41 Raiha St Porirua W...

Reviews: