Installation:
The installation must be realized in accordance with IEC/EN 60079-14, GOST IEC 60079-
14, and/or in accordance with the national requirements. This equipment must be installed
and used only by qualified personnel, having knowledge concerning electrical equipment for
use in potentially explosive areas containing gas and/or dust. Qualified personnel must have
knowledge regarding the types of explosion protection. This equipment is intended to be
used in zone 1, 2, 21 and 22 for groups IIB+H2 and IIIC with temperature class T5 or T85°C,
it is necessary to verify if this equipment is in accordance with the atmosphere where it is
installed.
Connections:
Electric parameters power control unit Maximum supply voltage:
POE+ IEEE 802.3at/af, and AC/DC 12-24 Volts 25W
The terminals are suitable for solid and stranded wires.- *See wiring Diagram Page
Cable Entries:
The cable entry must be made in order not to alter the specific properties of terminal housing
compartment. The connection to the external circuits must be realized by cable glands or
pipe fittings covered by a separate certificate(s). If a cable gland is not used, or an entry is
open, the entry must be closed by a stopping plug covered by a separate certificate. The
thread diameter of the cable entry is ¾ inch NPT.
This equipment can be used with different voltage and power, the nominal parameters are
specified in the manual.
Cable: cable must be tested and certified for temperatures of 80°C orhigher.
Fiber Cable:
Use a suitably certified optical fiber cable and internal connections shall
comply with requirements of IEC/EN 60079-15 and or, GOST IEC 60079-15
**The F101-P1377-BD does not accept optical fiber**
Equipment Modifications:
This equipment must be installed and used in strict accordance with the instructions given in
the user documentation. This equipment contains no user-serviceable components.
Unauthorized equipment changes or modifications will invalidate all applicable regulatory
certifications and approvals.
General Safety and Operating Information:
F101-P137(5,7,8)-BD REV 2 114309212018 F1XX
SERIES INSTALLATION REV-2A
11