54
SLC 500
™
50 KHz Counter / Flowmeter Module
Codes
I/O error codes appear in word S:6 of the SLC processor status file. The
first two digits of the error code identify the slot (in hexadecimal) with
the error. The last two digits identify the I/O error code (in hexadecimal).
The error codes that apply to your module include (in hexadecimal):
• 50–5E
• 71 (watchdog error)
• 90–94
For a description of the error codes, refer to the Allen-Bradley Advanced
Programming Software (APS) Reference Manual, Allen-Bradley
publication 1746-6.11.
No Signal
After reviewing your configuration and LEDs for errors you may want to
check the input register Rate word for any indication of signal. If status
bit 1 (Counter Input State) is high and status bit 11 (Rate Zero) is high you
may require a 1 to 10k
Ω
pull-down resistor (depending on the in-put
device) between your channel input and channel common.
If you have an open collector output or a relay or contact type output you
may need the pull-down resistor. Refer to your sensor documentation for
addditional information.
Verify that your input level thresholds are matched to your configuration
word input range.