10
SLC 500
™
50 KHz Counter / Flowmeter Input Module
Data Format
Counter mode
Max Binary Value: -8,388,608 to +8,388,607
Rate mode
Max Binary Value: -32,768 to +32,767
Isolation
Channel to Rack
1000 VDC Continuous
Optical & magnetic
Channel to Channel
0VDC
Input Protection
Max input voltage ±100VDC, 150VAC peak
Max input current ± 5mA@100Vp
Power Requirements
CTR4
CTR8
Internal rack +5v
175mA
225mA
Internal rack +24V
75mA
125mA
Table 1.2. Physical specifications
LED Indicators
Module Status
The Module Status LED indicates the status of the power up
self test. The LED is on when the module is ready. Any self
test error is indicated with a blink code.
Channel Status
CTR4 - 4 Green LEDs
CTR8 - 8 Green LEDs
The 8 Channel LED’s indicates that a channel is enabled.
Terminal Block
24 pin removable connector
Wire Size
One 12 AWG to 28 AWG wires
Torque .5nm, 4.5 lb.in.
Table 1.3. Environmental specifications
Temperature / Humidity
Ranges
Operating Temperature
0-60degC (32-140F)
Storage Temperature
-40 to +85degC (-40 to + 185F)
Humidity Temperature
5% to 95% non-condensing
Certifications
UL508 CUL& Class 1, Div II, (CSA equiv.)
FCC Part 15 class A CE Compliance to EN
61010-1 and EN 61131-2, EN50081-2, EN50082-2.
Summary of Contents for 1746sc-CTR4
Page 2: ......
Page 4: ......
Page 26: ...26 SLC500 50KHzCounter FlowmeterInputModule ...
Page 42: ...42 SLC500 50KHzCounter FlowmeterModule ...
Page 50: ...50 SLC500 50KHzCounter FlowmeterModule ...
Page 63: ...AppendixA FloatingPointRateMode 63 ...