Chapter 1: Module Overview
1-3
User’s Manual Pub. 0300181-07 Rev. A
Section 1.5
Detailed Specifications
Table 1-1. Thermocouple Temperature Ranges
Specification
Description
Configuration
4/8 Channel of differential counter inputs 2/4 Channels of quadrature
encoding 2/4 Input enable Control lines
Input Modes
DC counter, AC flow meter
Voltage Range
AC 0-30 VP
5 VDC
12 VDC
24 VDC
VIL
-50 mV
1 V
3 V
5 V
VIH
+50 mV
3.5 V
9 V
13 V
Vmax (CE)
±75 V
±75 V
±75 V
±75 V
Vmax (UL)
±100 V
±100 V
±100 V
±100 V
Current Range
5 mA maximum at 120 V
Input Impedance
Rin greater than 10 ohms when within -10 V to +12 V range.
Rin = 25 Kohms when outside of -10 V to +12 V range
Cin 100 pF
Input Filter Off
Cin 1000 pF Input Filter On
Counter Speed
DC Inputs
0 Hz to 50 kHz
AC Inputs
0 Hz to 50 kHz
Input Frequency
DC Inputs
1 Hz to 50 kHz
AC Inputs
1 Hz to 50 kHz
Counter Enable Input
VIL
1.0 V maximum
VIH 3.5 V minimum
Vmax 75 V
Input impedance
25 Kohms
Input Filter:
Digital Filter
Digital Filter
Analog Filter
50 kHz (Default)
30 kHz
15 kHz
Min Pulse Time:
DC mode
External Enable/Disable
8 us
Enable and Disable setup time = 20 us
Channel Update Time:
Counter Output
Rate Output:
Rate Instantaneous Mode
Rate Average Mode
Scaling OFF ON
4.00 5.6 (msec per channel)
4.00 5.6 (msec per channel)
1.00 1.00 (sec per channel)
Summary of Contents for SLC 500
Page 1: ...User s Manual Pub 0300181 07 Rev A ...
Page 8: ...viii SLC 500 50 kHz Counter Flowmeter Input Module User s Manual Pub 0300181 07 Rev A ...
Page 24: ...2 10 Chapter 2 Installation and Wiring User s Manual Pub 0300181 07 Rev A ...
Page 55: ...Chapter 6 Testing Your Module 6 5 User s Manual Pub 0300181 07 Rev A ...
Page 56: ...6 6 Chapter 6 Testing Your Module User s Manual Pub 0300181 07 Rev A ...
Page 60: ...7 4 Chapter 7 Maintaining your Module and Ensuring Safety User s Manual Pub 0300181 07 Rev A ...
Page 64: ...A 4 Appendix A Floating Point Rate Mode User s Manual Pub 0300181 07 Rev A ...