5-4
Chapter 5: Programming Examples
User’s Manual Pub. 0300181-07 Rev. A
Limit are multiplied by 256. The resolution of the Preset and Limit values in the
standard mode is one count. The resolution in the extended mode is 256 counts.
Count Size
±32 K
±8 M
Description
Preset Value
1000
256,000
= 1000 × 256
Limit Value
100
2560
= 100 × 256
Section 5.5 Using
Scaling with Count
and Rate Outputs
Count Output:
Counter output scaling is applied using the K & M scale factors. When a scale
factor is applied to the counter the Counter Output Register = (Raw Count * (M
factor /10000) * 1/ K Factor). When a scale factor is being used the Preset and
Limit flags are also scaled.
Rate Output:
Rate output scaling is applied using the R scale factors. When a scale factor is
applied to the module the Rate Output Register = Incoming frequency/R Factor.
When a scale factor is being used the Rate Limit flag is also scaled.
Example:
If a rate factor of R = 2 is programmed into the module, the Rate Limit value is
set to 10 kHz
In this example the Rate Limit Flag would be set when the input frequency is
greater than or equal to 20 KHz.
Rate Limit Flag = Input Frequency * R factor
Rate Limit Flag = 10,000Hz * 2 = 20,000Hz
Section 5.6 Application
Meter Proving
The 1746sc-CTR4/8 module provides a feature that allows you to perform meter
proving functions. A typical meter proving-application includes two detector
sensors that are located a fixed distance from each other within a section of pipe
used specifically for meter proving.
The operation does not disrupt the in situ flowmeter’s operation.
Using the external gate enable to start and stop count functions enables the user
to count pulses as fast as 20 microseconds to an accuracy of 1 count.
The following example wave form represents the start and stop transitions on the
Summary of Contents for SLC 500
Page 1: ...User s Manual Pub 0300181 07 Rev A ...
Page 8: ...viii SLC 500 50 kHz Counter Flowmeter Input Module User s Manual Pub 0300181 07 Rev A ...
Page 24: ...2 10 Chapter 2 Installation and Wiring User s Manual Pub 0300181 07 Rev A ...
Page 55: ...Chapter 6 Testing Your Module 6 5 User s Manual Pub 0300181 07 Rev A ...
Page 56: ...6 6 Chapter 6 Testing Your Module User s Manual Pub 0300181 07 Rev A ...
Page 60: ...7 4 Chapter 7 Maintaining your Module and Ensuring Safety User s Manual Pub 0300181 07 Rev A ...
Page 64: ...A 4 Appendix A Floating Point Rate Mode User s Manual Pub 0300181 07 Rev A ...